I had the same problem at one point. The contactor was the cause, it was stuck on the closed position. Good video. We have to thank the guys who take time to share information.
@noelelnolo9642
Жыл бұрын
Excellent video, great job looking for the culprit.
@Buster-im5so
Жыл бұрын
Dave, this problem plaques my condenser as well. Now I'll look for frayed wires. Thanks dude... yours is the only video I've found on this subject.
@RScottMelton
Жыл бұрын
I would suspect the wire was like that from the factory. It just took years of vibration and insulation degradation to finally short it out. Good troubleshooting logic and info. Thanks!
@huntgibson3716
2 жыл бұрын
Great fix Dave. That's a new one for me too. In my experience, this situation has always either blown the low voltage fuse or tripped the breaker. Thanks for sharing!
@ApartmentMaintenancePro
2 жыл бұрын
Thanks for watching Hunt!!
@Honestandtruth007
9 күн бұрын
@@ApartmentMaintenancePro My Goodman has Same issue. I appreciate for the video 👍
@kangzau1006
Жыл бұрын
Very cool that you did the troubleshooting directly on camera
@MediaArchitects
Жыл бұрын
You helped me take care of my 92 year old mother’s Air conditioner that wouldn’t shut off. The aged electrical contactor was stuck in the down position. I will be replacing it thanks to you.
@davidjoines8497
Жыл бұрын
Thanks for your posting I checked my capacitor and yes I had a dead mouse across the capacitor I cleaned it off and by gosh it now works perfectly. So grateful for your insights. Thanks again
@chazbOE39
Жыл бұрын
I had this issue on my Bryant plus 80 Conditioner, and i agree with this guy about swap out the CONTACTOR, IT WAS STUCK ON
@bobster99
Жыл бұрын
I appreciate you posting this video. My problem was actually the Contactor. I am in Florida and ants seem to love electrical boxes and that includes the A/C Shut off and pretty much any place that is dark and protected. I found the electrical connection area of the Air Conditioner filled with ants and it appears that a couple of unlucky ants got between the contacts and when the thermostat energized the contactor relay the ants got fried and stuck the contacts together. Luckily it is winter in Miami and I was leaving for the weekend so I didn't need A/C and had time to order a new contactor and a spare capacitor (they don't seem to like the heat down here either). If this would have been August I bet I could have pried the contacts apart and it would have worked long enough to order a new one but luckily I didn't have to find that out. Thanks Again!
@ApartmentMaintenancePro
Жыл бұрын
Glad you got it goin!!
@DJV94022
3 ай бұрын
You mean termites 😂
@Honestandtruth007
9 күн бұрын
Thank you for your Video I think I will Look into inside the Compressor wires. Maybe it Short too😮😊@@ApartmentMaintenancePro
@michaelfarfan3072
7 ай бұрын
Great job. Glad you searched for the main issue. And, not just changed out contactor. Thanks for the video it will Definitely help me.
@thriftypsgr
11 ай бұрын
Headed to a service call right now for this issue. I hope this video helps
@remmyerickson4779
5 ай бұрын
I loved the troubleshooting. It helped me check off what it could be.
@joeyysossa4144
2 жыл бұрын
Great job...visual inspect is always first...
@rickavelar62
4 ай бұрын
Great video, I just had a hockey puck style safety switch and condensate pump installed inside my condo.I noticed the next day, my fan outside runs all the time with a/c off ? , and the lines are freezing up.I'm thinking they didn't wire it up correctly, I'm calling the HVAC company, to come back to see if they caused the problem, or maybe it's just a coincident . Thank you for helping me with the video !!!
@ApartmentMaintenancePro
4 ай бұрын
Hard to tell without a full diagnosis but good call on getting the hvac company back out 👍
@LexVance
2 жыл бұрын
Crazy! Making memories Dave! 🤣 Great video man!
@ApartmentMaintenancePro
2 жыл бұрын
Thanks Lex! Always fun to run into crazy issues like this :) well, sometimes
@fernanduslewis2101
Жыл бұрын
dude you save me....this one video was the reason mine was doing the same thing.....wire melted on canister all i had to do was tape and separation witn zip ties....keep doing your thing dude....i bought new contactor which was defective from amazon....and a capacitor and i had a new defrost board from years back....
@ApartmentMaintenancePro
Жыл бұрын
Nice job! Glad you got the problem fixed lewis 🛠
@Honestandtruth007
9 күн бұрын
How funny it's my Goodman has Same issue Compressor turned On and Off. ...even i changed New Contactor single Pole as Original. Oh boy I have to LOOK for the SHORT too😮😔
@demtriustriplett9222
2 ай бұрын
great gaddamit work buddy i have the same issue currently .in chicago ,thanks !!
@carlgreen2232
2 жыл бұрын
I have seen heat pumps back feed lv from the relays inside and do this as well..Paint pens work great to label the units also.
@ApartmentMaintenancePro
2 жыл бұрын
Right on Carl thanks for the input!
@fernanduslewis2101
Жыл бұрын
please explain about back feeding to the air handler relay?
@EvanT1995
2 жыл бұрын
Great video and an even greater view from up there
@ApartmentMaintenancePro
2 жыл бұрын
Thanks Evan 🙏
@garrettmandujano2996
Жыл бұрын
Just had this come up for me, we’ll see if mine is the same fix, thanks!
@ApartmentMaintenancePro
Жыл бұрын
What did you find?
@garrettmandujano2996
Жыл бұрын
@@ApartmentMaintenancePro a customer called saying this was their issue, I asked if the batteries had been changed in their thermostat, they told me they had. The first thing I checked was the thermostat and I noticed corroded old batteries, so some new ones went in and the confesor fan stopped running upon receiving the new signal.
@ApartmentMaintenancePro
Жыл бұрын
@@garrettmandujano2996 Good first instinct 👍
@billbliss2500
Жыл бұрын
I’m glad I watch this because I have a carrier unit that the condensing fan motor keeps running, and the thermostat is satisfied in the blower fan motor in the furnace is shut off. However, I replaced today the capacitor that was bad, but the condensing motor now stays running and is never satisfied and shut off. I also checked the contact block and the contacts are in perfect shape. I also had the other day refrigeration guy come in at 11 ounces of refrigerant, that’s all it was low. So I don’t understand why the condensing fan motor continues to run???? If I turn The thermostat to off it Drops the coil out on the contactor. I also Took out the condensing fan motor when I went to get a new capacitor. I mentioned that because the video showed the wire that was shorted to the frame but in this case the wires were fine no shorts to ground.
@ApartmentMaintenancePro
Жыл бұрын
It’s getting constant power somehow. Possibly miswired
@deepbludude4697
7 ай бұрын
Good job Tshooting! So im dealing with a condensor fan that started running slowly constantly with Tstat off, its been in heat cycle for 2 months. im guessing maybe the cap is bad or a short. Gonna go out there in the morning and inspect thanks for posting.
@DJV94022
3 ай бұрын
If its a lennox the defrost board starting off new out the box can have the defect of internally having yellow and red bridged when its suppose to be seperate circuit
@mrsalsamafiatv235
12 күн бұрын
Nice job, thank you.
@theopappas1890
8 күн бұрын
I hope this wasn’t the issue at a recent Goodman call
@cr-qk4wd
2 жыл бұрын
Awesome vid, Thank you.
@retrothruster2539
2 ай бұрын
This saved me! Mine turned out to be the contactor like the post below, very much appreciated!! Sub'd/liked!!
@jcaleca60
Жыл бұрын
That's a hell of a critter factories out west have to buy special Transformers to create another phase this little critter created a sine wave to get to 220 very smart critter
@sixtygrit9944
2 жыл бұрын
Good find!
@rionavarro8381
3 ай бұрын
nice work Mark Ruffalo
@justwork_hvac
2 жыл бұрын
great fix.thanks for sharing
@BlacHaze78
11 ай бұрын
Why didn’t you put in a rubber grommet? The problem will eventually happen again.
@PhilipAlonzo
2 жыл бұрын
Thats a cool tester
@franciscojavierestrada7585
Жыл бұрын
Yes i hate those single pole contactors have to be extra careful
@marcos.aguilar1013
9 ай бұрын
Mine is strange, I turned the heating on and it's just not stopped running now for about 2 weeks. I'm gonna figure out how to fix it now.
@TheColergruver
2 жыл бұрын
Wow, good find!
@ApartmentMaintenancePro
2 жыл бұрын
Thank you!!
@larrynone6354
4 ай бұрын
I'm having this problem and I can't figure it out. I replasterered the motherboard, and it does exactly the same thingI replaced the contactor and the same I've checked all the wires and no shorts. Is it possible for the copasitator to keep it running.
@michaelsorrentino-cx5nx
3 ай бұрын
Same problem found shorted fan wire
@MRM-wp4gr
Жыл бұрын
I have this same problem on a Guardian 5 ton unit. All the wiring looks fine and all connections are tight. Could it possibly be a bad contactor? Or what else could cause this. The fan seems to be getting 110v from somewhere because it only turns slowly and heats up to 130* until the compressor kicks on and brings the fan up to full speed, then the motor cools off.
@alexgg7499
2 ай бұрын
Mine the thermostat moves itself to 65 keep running what is it
@edbtzkhud
Жыл бұрын
My compressor stays running for about a minute or so after the inside unit turns off. Any idea what it could be?
@ApartmentMaintenancePro
Жыл бұрын
Contactor could be arcing welding itself shut. Of course, this is just a guess that could be wrong
@crama1963
4 ай бұрын
Excellent
@LuisFlores-hl5zf
9 ай бұрын
You got it bro
@rifathasan413
5 ай бұрын
Thank you
@blackarm3265
Жыл бұрын
Thanks very good
@curtisthrow5743
Жыл бұрын
I used markers but I label inside power block boxes
@ApartmentMaintenancePro
Жыл бұрын
I'd rather see that than markers exposed to the outside. Paint pens and markers will last maybe a few years before fading when outside.
@brandonpierce1729
Жыл бұрын
Would this make the inside fan blower run continuously as well?
@ApartmentMaintenancePro
Жыл бұрын
No, but a bad relay or thermostat would
@jamesmungal2559
2 жыл бұрын
Why it didn't tripped the breaker? Since it was a short to ground?
@carlgreen2232
2 жыл бұрын
Breaker is far away sometimes if they are far enough it won't trip.
@fernanduslewis2101
Жыл бұрын
@@carlgreen2232 mine is doing the same thing it kicks the breaker when u turn on the air and the outside unit breaker kicks
@alfredhines505
6 ай бұрын
Bro, u have a welded contactor.
@HandyLotion
Жыл бұрын
Shared
@swflscratcher5893
Жыл бұрын
I got the same problem but capacitor is replaced and it’s still doing it
@MaintenanceGuy-sp1ll
9 ай бұрын
It's more than likely the contactor.
@swflscratcher5893
9 ай бұрын
@@MaintenanceGuy-sp1ll bope
@swflscratcher5893
9 ай бұрын
@@MaintenanceGuy-sp1ll nope
@MaintenanceGuy-sp1ll
9 ай бұрын
@@swflscratcher5893 if it's not the contactor which is the most common problem than a bad relay or wire
@c21meister
2 жыл бұрын
Goodman and their horrible wire runs
@atanaciomaldonado3943
Жыл бұрын
Haaaa is something wrong everyday see something
@minutebooks3245
25 күн бұрын
Another video that is directed at people with HVAC experience. The rest of us idiots are completely lost. Lots of terms that aren't explained. I have no idea what you are doing or why.