*Used to supplement the up stairs when it gets hot outside this works very well and **Fastly.Cool** Also works good when the upstairs gets too hot in the Winter from the heater.*
@jaykemm3472
2 жыл бұрын
I work for NASA. And when we do space walks to go out and repair condenser fans, this is exactly how we do it. Great Job.
@1ndeloach
11 жыл бұрын
I'm an HVAC tech an your videos just made my job a lot clearer. thanks. and please keep creating more videos.
@wizbang68
4 жыл бұрын
Nice explanation! Looks like whoever serviced the unit (replacing the fan, I would guess) didn't go to the trouble to secure the wires that were used to set the fan rotation direction.
@DanNA-ww4gv
9 жыл бұрын
very insightful video. very helpful to have the schematic and resistance values for reference or else u could have condemned a good fan motor at your initial check.
@DIYTinker
11 жыл бұрын
Thanks for pointing that out. check out the schematic in my description. that schematic is for this unit, and exactly describes what you said.
@emilylor5328
Жыл бұрын
Purchased: August 2023 - still works GREAT!I kzitem.infoUgkxxsUnXhGsSJLim_XnMHyQK0u3XVaW-CGn live in a studio and during the summer it gets scorching hot - really old building with no ac units. I can’t express how EASY it was to install. This unit has been a life savior during the summer and some days during other seasons where it can still be a bit warm at night. In this small place is my friend, a husky, poodle mix and myself. We need AC - lolI don’t use the dehumidifier option - I’m not sure if it will leak in my house, since I did not install the small draining hose that came with it. May look into it late but I don’t worry about much humidity in the apartment. I don’t understand why the negative reviews since all things mentioned, I personally did not find issues with. Definitely worth it!
@DIYTinker
11 жыл бұрын
ha.. yes, i removed it for now. Was considering remaking it again. I should have it up again soon. thanks for asking, it made my day :)
@DIYTinker
11 жыл бұрын
i was also surprised. But that's how it was originally wired, the schematic agreed with the wiring, and i couldnt argue with the resistance measurements. I'm not a HVAC professional, so, i might be wrong.
@vmukal8430
6 жыл бұрын
Well done video - just one comment that when measuring resistance between motor windings (or any other electrical circuit), at least on of the leads should not touch your fingers. Around 8:00, the wires are being held to the leads by the fingers - this may affect the readings depending on your body resistance. If you had sweaty hands, your readings may be inaccurate and not add up for the total winding reading.
@bzd16b
11 жыл бұрын
Common is where the two windings meet and is connected to L1.run is the winding with less resistance and connected to L2
@oafyvonskidmark316
6 жыл бұрын
I was just going to say you put the Common terminal where the Run terminal goes, Common is the point both windings are connected to each other.
@quangnguyen-hq1bc
10 жыл бұрын
Thank you .It is very useful for me. I don't get it in class .God bless you .
@cruzingpapa
11 жыл бұрын
Didn't you notice the condenser coil was completely stopped up with dirt? That may have been the reason the other motor went out. The easy fix isn't always the best fix.What was your liquid line pressure? I bet it was very hi if you checked it.
@codylynd8097
10 жыл бұрын
Very Good information here a lot of people will face this problem Fast Ac Repair San Marcos Texas
@crossh12
11 жыл бұрын
Nice job! I'm going to try and fix mine tomorrow.
@GalaXy808
11 жыл бұрын
Now I got it,they got hit by the blade that's why not working? Wow this is a good discovery.thats why sometimes it's good if we chech before we call the pro.thank you sir
@DIYTinker
11 жыл бұрын
well. the motor went out becuase the wires were chewed. you can see it at 5:40 in the video. But you are right about having a clean coil, and no i didnt check the liquid line pressure. maybe ill ask my wife to get a gauge for xmas :)
@lkw5699
4 жыл бұрын
Excellent troubleshooting. Wish you were my ac tech
@wata_laf
Жыл бұрын
Ok, In your diagram I would like to clarify that the common and start don’t share a cap. What I think ur trying to describe is the common on the capacitor, btw two separate things. The common winding is a main leg and should be at the point of your diagram where ur “run” is oddly located. The run leg shares cap with start leg winding allowing for starting/operating torque of motor.
@aircooledtx
7 жыл бұрын
Always connect brown to F cap,yellow to C on cap, black to contactor, cut-brown/white strip /out . yellow and brown/white are same wire inside motor.
@DIYTinker
11 жыл бұрын
i agree. its a long story why i have it like this. watch the schematic video i made, and you might understand why.
@albundy3763
8 жыл бұрын
your condenser look full with dirt will effect cooling capacity spray and wash be sure using not so strong water pressure not to bend soft aluminum cooling fins . first spray some kind cleaning agent then wash sprying from inside out while fan out keeping clean those fins are can make your comprosser life longer and save also electricity
@MrGGPRI
7 жыл бұрын
I did this once; sprayed my GM van AC condenser with HP hot water after colliding with a mass of bees moving their hive. Flattened every condenser fin and finally had to replace the radiator-- $$$$ lesson.
@oafyvonskidmark316
6 жыл бұрын
Use condenser coil cleaner , the foaming type, it will push the debris out of the fins and strip the coil clean and bright.
@jasonray8530
7 жыл бұрын
A quick visual inspection would have saved us a lot of time. When you have 6 or 7 service calls scheduled you learn to do this. 80% of the job is common sense.
@DIYTinker
11 жыл бұрын
thx for the kind words. will do :)
@yoshimra
8 жыл бұрын
Holy cow, clean that system! Look at all the dirt. No wonder why it broke, air can't get through that dirt.
@solow46
11 жыл бұрын
Right after pulling out the disconnect I would check if the motor spins freely, the problem could be mechanical. After eliminating the possibility of mechanical malfunction I would troubleshoot electrical side of the fan.
@DIYTinker
11 жыл бұрын
yes, its noted in the middle @ 2:27
@highVoltage208
11 жыл бұрын
Good job dude not bad for a DIY I'm tech n that's a clear explanation
@CoolasIce2
11 жыл бұрын
Very informative, but are you sure the fan diagram is correct? Should the Run and Common terminals be switched? i don't know. This is a 240 VAC motor.
@petesingh292
8 жыл бұрын
I hope you corrected your wiring diagram common wire, the rest good to go
@patadegrillo007
10 жыл бұрын
Good video, very informative.
@DIYTinker
11 жыл бұрын
nice. keep us updated.
@mmichaeldonavon
11 жыл бұрын
I liked the video, but have a question: Was the "new" motor (which had the damaged wires) installed incorrectly? Seems so. Thanks
@JoseJimenez-ee2gr
Жыл бұрын
Thank you for the video good job!
@gauravcrazykumar
9 жыл бұрын
first of all, very insightful video. I have one question though, while you have taken out the fan, there were four wires and you have connected YELLOW-PURPLE and BROWN-ORANGE for CCW direction spin.This moment only two wire is coming out of fan. My question is while you were measuring the resistance, you have taken the measurements between Brown-black , Black-Yellow & Yellow-brown. Here there are three wires. I am so confused. Is the brown wire is the same on coming out of fan or there is some more connections which is not shown in video. Hope this is not stupid ques??
@DIYTinker
9 жыл бұрын
Gaurav Bhadani the fan directional wires are different than the fan wires. If you are referring to 7:18 when i measure the fan resistance, then that was explained in 1:38. Hope that helps.
@RS-tz2zn
9 жыл бұрын
G Vik That was a good question...as I was originally confused as well...if you look at 5:43 in the video, you can see both sets of wires...
@michaelsolow4676
8 жыл бұрын
+G Vik If you are only looking at the colors of wires, you are missing the "big" picture. It's easier to understand the function of a motor than to memorize wires.
@ANDREASRIAL
9 жыл бұрын
very good video, thanks for giving All this great information
@klekotko
8 жыл бұрын
Very helpful, and I have the same issue, I replace capacitor, didn't check contractor yet tough, fan motor doesnt turn, and presents resistance when manual spun.
@IshockO
8 жыл бұрын
Contactor
@whiteboyfromernul
7 жыл бұрын
if like his,the compressor was running and not the fan,that tells me its not the contactor or neither one would run,if the fan does not turn freely its no good
@IshockO
7 жыл бұрын
M Norm if compressor was running and fan wasn't it could be the motor or run cap
@TheTrhome
7 жыл бұрын
My fan will only run if I give it a Kickstart, but it will only run for a about 3mins and shuts down and it will not come back on until I shut the entire system down for 30mins or so. I've already replaced the cap. Would this likely be a bad motor?
@whiteboyfromernul
7 жыл бұрын
if you know how you could connect to the power going to the fan,put it to fan "on" and see if you have 240v,if so and you have a good capacitor i would suspect the motor and we are talking about the air handler?and since you say it has a capacitor its not an ecm motor?
@adamspokes81
11 жыл бұрын
Hi there.. You recently posted a video on understanding electrical diagrams/schematics and can no longer find it... Was it removed?? thanks
@360xi
8 жыл бұрын
Very well edited video let alone very informative!!!
@eman3208
8 жыл бұрын
Thanks man clear explanation ... thanks
@DIYTinker
11 жыл бұрын
yes, the basics to all single phase motors are more or less like this. you can check out kzitem.info/news/bejne/026CqmqorXediI4 for the compressor
@TheScrappingJeahaha
11 жыл бұрын
does this wiring also work with the compressor or with other electric motors ?
@slickusaf78
6 жыл бұрын
Where does the 5th or common wire go from a new motor? My red and black go to the controller board
@bigbite9804
9 жыл бұрын
Dear friend u are very smart I appreciate but I said a refrigerator??? means less amp not same like a window a/c it's taking 10 to 12 amp..
@mauricewilley5309
9 жыл бұрын
+asifkhan khan Air conditioners have much greater working loads than refrigerators. Refrigerators cool down 30 cubic feet in an insulated box, air conditioners cool down over 5, 000 cubic feet of poorly insulated space. Amps directly correlate to the work load a motor can support. That's why they cannot be compared. Cheers.
@michaelsolow4676
8 жыл бұрын
+maurice willey everything is relative, volume, temperature and operating pressures are different
@bryandellinger2263
7 жыл бұрын
how did you figure out the correct resistance reading should be ?
@dizzolve
8 жыл бұрын
How do I find out the proper wiring for my capacitors I have an old Trane from the 80s
@DIYTinker
11 жыл бұрын
thanks. your too kind.
@albertogutierrez2534
10 жыл бұрын
once again thanks great info.
@unnikrishnanmanurapalli1624
8 жыл бұрын
In which direction the fan in the out door unit fan should be run in case of three wires connection
@mohdnizam807
10 жыл бұрын
one question if suctionpresser 55 how much want dicharge presser?
@edwardburnsburns5307
10 жыл бұрын
the fan motor is a indoor blower motor it was riged to work so it did not last because it 1 was incorectly wired. 2 it is not a water resistent motor and this is not a good video to learn from because he should haave from the beginning told every one it was the wrong motor . and he is checking his resistance the wrong way , you need to pull your wires from the contactor and capacitor first then check ohms.
@cruzingpapa
11 жыл бұрын
Starting the motor with a bad capacitor is a bad idea. The motor windings will overheat and hopefully open but very likely damage the motor. Buy the 10 buck cap before you have to buy a motor also.
@gloiban
7 жыл бұрын
Common and run are in the opposite places on your schematic.
@BM-jh3gx
9 жыл бұрын
Can a bad fan motor damage a new capacitor? My fan stopped spinning in my ac unit. I put in a 40/5/440 capacitor (made by different company than what was in unit...both are 40/5/440). The fan ran for about 45 min then stopped and would not turn on again. Both capacitors are rated -6% +6%...whatever that means.
@donniethorntontemp
9 жыл бұрын
no, a new cap cant damage a fan motor. you might have had a fan going bad. Also, you might have a wrong rating capacitor in the beginning (if the unit is old, some HVAC tech jsut put wrong stuff in) along with an aged fan will also cause issues. Finally, you might have hooked it up wrong or have loose contacts or now another part isnt work. e.g. the contactor/relay or fuse.
@lloydd.2306
10 жыл бұрын
Is that correct???the common & start terminal of the fan motor connected to the capacitor???or maybe is it run & start terminal that must be connected to the capacitor???kindly verify..thanks
@DIYTinker
10 жыл бұрын
The label for common, run and start on this motor is correct. Other motors can have common and run label switched. It doesnt matter what its called for either common and run. What is important is the 120VAC on both R and C. you should always look at the schematic and see what orientation your unit has.
@bbal78
10 жыл бұрын
how come the yellow wire at 3:37 goes to the Terminal, it should go to the capcitor ?
@Galaxyngc7331
9 жыл бұрын
When you are taking ohm measurements @ 8:15 is the last measurement suppose to equal the combination of the first two measurements?
@jjenson2006
8 жыл бұрын
Yes, but the third measurement was unnecessary because it couldn't possibly measure anything else besides the two resistances added together.
@bigkool35
11 жыл бұрын
? ..if I get it 230 volts going to the fan motor and the cap is bad will the motor attempt to start
@armindoferreira5886
8 жыл бұрын
In the schematic the run and comon is in wrong place
@user-ge6ce2lu1v
5 жыл бұрын
That is true, but wiring a compressor according to that schematic still works.
@harshidsony
5 жыл бұрын
Com go to compressor and no go to indoor in split AC. Is it right?
@MrMac5150
9 жыл бұрын
Needs to be counter clockwise pulling the air up, cuasing a vacuum around the condenser.
@tboneproductions2453
6 жыл бұрын
Nice job
@DIYTinker
11 жыл бұрын
thx! really appreciate that :)
@reggiemilla8835
9 жыл бұрын
lol, that was cool, I like those types of srvc. calls they keep me sharp and on my toes with troubleshooting.....
@Phxzaddy
10 жыл бұрын
Everything starts up right or the way it should, but after about less than 10 minutes the fan shuts off, there's really loud hissing and one of the copper pipes is burning hot. Any advice?
@vicg5189
10 жыл бұрын
Question , what is the problem for this fan motor ? shoted wire?
@DIYTinker
10 жыл бұрын
@ 5:41 the wires arent connected
@DIYTinker
11 жыл бұрын
the motor will attempt to start, but most likely it cant. you could use a stick, push the fan with the stick, and it might start running.
@jenko701
11 жыл бұрын
You have the common and run reversed in the diagram.
@SB9P4
5 жыл бұрын
WELL, OPEN THE FAN AND SEARCH A LITTLE FUSE OR RESISTOR IN ONE OF THE WIRES AND CUT ,NEXT MAKE A NEW CONNECTION, AND THAT FAN CAN BE GOOD AGAIN.
@nb4776
8 жыл бұрын
THANKS for the video. my ac fan has brown,black and yellow . total 3 cables. can u tell me how to taste my motor please? thanks
@LubaLuba1
10 жыл бұрын
how can I check thermostat 24 v to ac outside what should my meter be set on??? my ac unit turns on when I put in the pull switch and the relay doesn't appear to be stuck or responding to thermostat so I will check for current to relay then I think wiring is causing this some how which means its bypassing relay. I cant figure it out.
@LubaLuba1
10 жыл бұрын
I already rectified the problem it was wired wrong then contactor was not pulling enough for contact so replaced contactor now everything running just find people don't hire AC person they will steal your money for something you can do. Very simple !!
@davidquezada50
6 жыл бұрын
Wow wish you were my neighbor. My ac is broken too My mother won't let me try and fix it
@heidis8713
6 жыл бұрын
Your mother is smart.
@eman3208
8 жыл бұрын
How about if instead of 42ohms you get 41ohms do you consider that a bad fan motor? how about if it happens with a compressor also just 1 ohms different is that consider bad right away?, just have this experience...
@whiteboyfromernul
7 жыл бұрын
no,it could be a couple ohms in either direction and considered good
@jddr.jkindle9708
8 жыл бұрын
Open toed sandles at a worksite - oh my. Safety violation. Your wiring diagram at 02:01 is wrong. C should be in between R and S.
@ronniezzzz
10 жыл бұрын
two separate caps are better than a combined one
@armindoferreira5886
4 жыл бұрын
… Common means feeding both windings R ( run ) and S ( start )!
@mrxyooj
10 жыл бұрын
hey i'm having the same issue here. problem is when i turn on the AC i can't hear the buzzing sound or a hum on the outside fan but my blower fan inside the furnace is on and is blowing warm air. My question now is.. the run/start capacitor bad? or is it the fan motor? help!
@DIYTinker
10 жыл бұрын
so, outside fan and compressor isnt on right? check the relay and capacitor: AC not starting up - Air Conditioner condensing unit lost power - Replace Contact contactor relay AC fan not working - how to repair broken HVAC Run Start Capacitor - air condition
@mrxyooj
10 жыл бұрын
DIY Tinker Hi again, checked both the relay and capacitor and looks fine. I had a local HVAC guy come out to rewire and bypass the wires coming from the circuit board to the cap and relay and now the fan kicks on like its suppose to without hesitation, but its tripping the house breaker. the guy says it looks like a motherboard or circuit board issue inside the unit is acting up. It will startup normally when I set to "cool" and "auto" on the thermostat but once it gets to the desired set temp the fan will stop, however if the house temp starts rising again pass the set temp, the fan will not startup. The only way I can get it to start again is by turning the thermo switch from "cool" to "off " setting, flipping/reset the tripped breaker and then turning the thermostat from "off" position back to "cool" Do you think its the thermostat thats acting up?
@DIYTinker
10 жыл бұрын
Hello Bye I think you should first check your breaker. Ive seen similar issue before and the breaker got old where it cannot handle its max current any more. That would be a cheaper and easier fix. If fixing the breaker doesnt solve it, then something is pulling too much current (e.g. your fan or compressor, etc...) But, no, i do not believe your control board would do that, and no i do not believe your thermostat would do that either. Keep me updated. this is interesting. p.s. i do have a video on replacing the breaker: how to repair replace broken circuit breaker - multiple Electric outlet not working - fuse box panel
@armindoferreira5886
4 жыл бұрын
… your schematic is very wrong, R ( run ) and C ( common ) have to change other way around and consequently the capacitor has to be connected between R and S !…
@bigbite9804
9 жыл бұрын
Can we make a airconditing like that using electricity same like a refrigerator? ?so everyone one can afford. ...🙏🙏
@DIYTinker
9 жыл бұрын
+asifkhan khan i think its called a window AC unit :)
@theshagboy1
5 жыл бұрын
How do I find the fan capacitor for a Trane model#YCX030G1M0AA ? The unit is about 20 yrs old and nothing on UTube looks like it. I got ZERO help when I called Trane other than call trane dealer....which is what I don't want to do
@grantfleming6860
8 жыл бұрын
Reverse common and run and your diagram will then be correct.
@charleswhiteaker8611
10 жыл бұрын
Ac unit making a slight humming sound and fan not spinning. Any advice?
@DIYTinker
10 жыл бұрын
How to fix your AC - Fan kicks on but Compressor Not Working - Replacing run start capacitor
@charleswhiteaker8611
10 жыл бұрын
See my fan on the unit isn't kicking on at all. And the sound doesn't seem to be as loud as usual turn on sounds.
@asrikelantan7445
10 жыл бұрын
Saya pelajar ilp jitra...
@asrikelantan7445
9 жыл бұрын
Salam
@eppakayalanaresh818
7 жыл бұрын
Hi my air cooler motor isnt working what i need to check pls let me know it was rotating slow in the morning and later it stopped working, later it was making hum sound and now i dont even here now. 1) is it shorted 2) capacitor fail or ....?
@stevenw4549
3 жыл бұрын
Sounds like the bearings are seizing up.
@aciheatingandcooling4516
8 жыл бұрын
If you are a new tech or a home owner, please please do not listen to this video. It is incorrect and misleading. The information is wrong and you will be misdiagnosing systems.
@whiteboyfromernul
7 жыл бұрын
Aci Heating and Cooling your right,some people dont need to make videos
@davidquezada50
6 жыл бұрын
Why is it wrong? Why didn't you say what's wrong ?
@INTERNA9
3 жыл бұрын
Thanx
@ljaureguiv
9 жыл бұрын
im pretty sure your 'c' Terminal of your fan motor never hooks.up ever with any capacitor..
@jeffegg2
Жыл бұрын
I had a bug stuck in the contactor once.
@dyamondbak1
10 жыл бұрын
i will try it
@user-tv4ej8ob3w
11 жыл бұрын
هناك خطا في الرسم التخطيطي في الفديو المعروض ال c منطقة التوصيل هي بدل ال r التدوير يرجى ملاحظة ذلك
@jollyscaria1922
2 ай бұрын
Power off and conatcter checking capciter buror after find ouf after fan strckup why reson strick up ok replcing dolveing ok
@kwsa4657
8 жыл бұрын
nice
@MrMac5150
9 жыл бұрын
You need to clean and wash out the condenser.
@GalaXy808
11 жыл бұрын
What did happen?
@CatalinFlorentin86
6 жыл бұрын
C terminal should be R terminal. That it is a big error.
@jollyscaria1922
2 ай бұрын
Solveing ok
@germanshepherdsman
8 жыл бұрын
GREAT JOB
@noorpecha
6 жыл бұрын
my window ac fan stop after 2 hour . but compressor are running normal .
@ronniezzzz
10 жыл бұрын
small continuity though fingers
@tomyang7788
10 жыл бұрын
How do you ground the capacitor , it says put hem to grond, but it looks like we are just touching one wire
@DIYTinker
10 жыл бұрын
grounding the capacitor basically means to short HERM to COM with one wire.