A couple of years ago my AC was not working as well as it should had the AC company come out and they told me it was low on refrigerant but they wouldn’t fill it up. They just wanted to sell me a new AC unit. Had another company come out top off the refrigerant and it’s worked great for the last couple years.
@HomeRapidRepair
Жыл бұрын
Great topic. We come across this one a lot during home inspections…
@fshn76
Жыл бұрын
All facts! Great info!
@drz400sy8
3 ай бұрын
What if the AC seems to be running fine with not short or long run times and blowing cold air; and the tech says the sub cool is low and superheat is high? This seemed odd that there would be low Freon. My evaporator is rusty but seems to be running fine. Could the system still be failing as it does not seem to add up. Filter is fairly new.
@w8what575
4 ай бұрын
A dirty evap coil that’s covered in hair and dirt will do the same thing as a low coolant freeze over will do…..I clean the evap coil every spring…
@YT-User1013
2 ай бұрын
How do you clean it? You can’t hose it, can you?
@FloydYoder-q1l
Жыл бұрын
5:28 Exactly my problem! Thanks for your help!!
@skipsaunders5974
Жыл бұрын
would be useful to see the symptoms for a split system using inverter compressors and Electronic Expansion Valve (EEV) technology
@moonglum101
2 ай бұрын
My Daikin isn't working. It's got rust on the inside. My other Daikin, exactly the same make and bought at the same time a few years ago, seems to still be fine. Go figure.
@DaDeMadewaves
Ай бұрын
If they are low on refrigerant they most likely have a leak
@knoxtrail5412
4 ай бұрын
Outdoor unit free online not cold no condensation no buildup replaced with brand new capacitor where should I go from here
@michaelbaldwin3356
Жыл бұрын
Everyone of those symptoms have about 4 other issues that could be the problem. Not to mention all these pm’s that loose refrigerant and then in 2 or 3 yr they have pay for refrigerant and possibly a leak test.
@John777Revelation
Жыл бұрын
I'm learning diy hvac. Fascinating. Very informative. Thanks for sharing. Much Blessings to you. 🙏 Lord-Jesus-Christ ✝c✝o✝m
@oldskoolwayy
4 ай бұрын
Your ac can be running hard because of your home having leaks and not insulated right
@TheStrafendestroy
Жыл бұрын
doesnt low refrigerant indicate a leak some where in the system
@NewHVACGuide
Жыл бұрын
Usually yes
@carole8551
2 ай бұрын
I thought these tips were helpful. Does the outdoor unit have a filter that needs to be cleaned? I change my indoor filter every 6 months.
@YT-User1013
2 ай бұрын
Not a filter but the fins on the outdoor unit’s coil may need to be cleaned from time to time depending on how much outdoor debris it’s taking on (leaves, pollen, dirt). Turn off breaker or pull the fuse, remove the top and shoot garden hose water thru the coil fins from the inside out. You may also get away with just shooting the coil fins from the outside in and not remove the top but that drops all the crap in the center and maybe on the compressor.
@tannermikal2
Жыл бұрын
… after 36 hrs of slaving away in dog days of summer I come to realize you’re explanation for low refrigerant and guarantee that’s what mine is bc tried everything else 🤣 it was leaking past pan too and then froze up and yea pain in the rear.
@gtpforever
Жыл бұрын
Nothing like opening up a coil box or plenum and finding it completely encased in ice.
@ryanbrown5334
Жыл бұрын
Or with an A shape layer of ice 2 inches thick on the outside of the case!
@gtpforever
Жыл бұрын
@@ryanbrown5334 lol I could imagine that. I haven't come across that yet myself. Probably because my office tells them to shut down the AC and turn on the fan. But I'm surprised I haven't seen it yet
@YT-User1013
2 ай бұрын
FYI for those who want to use a hair dryer to thaw it out, turn on the heater to thaw it out.
@michaelp9276
Жыл бұрын
Thanks a lot for the vid! I have a strange problem with my indoor unit- have to say it is just a simple split unit with one wall mointed indoor room unit and an outdoor unit. The catch pan as well ad the condensate line is clear and working. The unit is also cooling but it is leaking on the flaps and drops on the floor. It seems that water is condensating on the flaps and air guides. Could that also be a symptome of low refrigerent? Thanks a lot and best regards from Germany!
@Sergio-ih6lk
Жыл бұрын
Thank you for your knowledge it is appreciated. I live in Miami Florida pretty hot here I gotta learn a little bit more about a c's Just saying
@ericacarriere8648
Жыл бұрын
Thank you for your content. It has helped me a lot. I live in Texas where the temps have been pretty close to HELL lately. It is 12:30 am right now. I put my thermostat on 68 at 5pm yesterday and it still hasn't reached temp. It's at 71 currently. The system does stop and start more frequently nowadays. We just got a new Goodman in 2020 and it hasn't had more coolant since we got it. Do you think it's time? Lastly, what's a fair price for coolant?
@NewHVACGuide
Жыл бұрын
Shop around if you're concerned about pricing. It may be time to have a tuneup/cleaning performed. But it should never be "time" to add refrigerant unless something is wrong. Thanks!
@Trust_but_Verify
Жыл бұрын
2020 unit should be using R-410a refrigerant, get a quote of how much per lb they charge. You should see ice build up around the pipes. Is the air coming out weak and not so cold? I have one 19 year old unit that hasn't needed refrigerant added.
@kevinhuggins3172
Жыл бұрын
My unit is taking a long time to cool. But only some times and not all the time. The line coming out of the compressor is not very cold. The line going into the A coil is not very cold. The air coming out of the vents is cold but not really cold. It was 103 today and it kept my 1400sqft house at 73° when it was set at 70°. Do you think I have low refrigerant symptom?
@jacksamulsen
8 ай бұрын
If it was 103 outside your unit was actually working just fine
@edzanjero353
2 ай бұрын
I have a 30 yr old Goodman R-22 and coincidental to a failed run capacitor and a disconnect fuse, the evaporator coils stopped outputting condensate. No ice on evaporator, no frost anywhere. On a hot day the evaporator will normally output a few gallons, but now zero. Register outputs are coolish, but not cold, and low volume, insufficient. Outdoor unit running normally, clean coils. Suction tube cool, not cold, no short cycling. I'm puzzled why one day there was normal evaporator output, but after repair, none. All values correct on compressor & new cap. Contactor measures normal. 26VAC from thermostat. Ideas?
@PHamster
Жыл бұрын
OMG!!! Congrats on the official Daikin sponsorship!
@NewHVACGuide
Жыл бұрын
Thanks!
@MrMadonis2010
2 ай бұрын
Hello, good video. Have a question. What is a good temp to set indoors when outside is 90F or more?
@craigclingman8693
2 ай бұрын
Great information, Josh!!! My air difference is 10 degrees F, so I'm thinking I need a recharge.
@donpablos123
7 ай бұрын
Can low refrigirant be another reason for high pressure in the system after 10 min of running, ie, above 550 psi (while only 270 expected under current conditions) ?
@tbone6354
5 ай бұрын
It is a good idea is to add 50ml of sulphuric acid to the compressor before regassing to reduce corrosion
@cyberGEK
3 ай бұрын
Sulphuric acid to reduce corrosion? I’ve heard a 1:3 molar ratio mixture of nitric acid/hydrochloric acid is much more effective. They say it’s the “King” of cleaning! 😂
@rolandberendonck3900
24 күн бұрын
The best thing to use is adding 320 ml of biological seawater to your compressor. If you don't have that use 315 ml distilled water with 14.5 grams of organic sea salt added to it. And don't! forget to wait 30 minutes before firing up the system again.
@acmm50
4 ай бұрын
Low pressure = low temperature = freezing of system
@jungapo2
Жыл бұрын
i don’t agree with you about using infrared thermometer. i have no problem using it to check if an a/c system has enough refrigerant.
@wannellalawson4001
3 ай бұрын
Our furnace is linking water underneath. The air conditioner man came out. He told us that we needed a water pump. He told us. Instead of letting water run down the pipe. Like it was doing. He will connect the pipe fm furnace. Run pipe outside the furnace. Run it into the bathroom. So it can be drained into our toilet. I do not lk that idea. Will this mess up my plumping? when an air conditioner person comes to your home. Does he check the air conditioner outside first? Thanks
@UserFriendly1989
3 ай бұрын
It's not necessarily bad for you plumbing but it will make a mess of your toilet over time. I personally think it's a terrible idea. Your furnace coil should be evacuating water through a trap and a pvc line into the drain in the ground. If applicable a condensate pump, but the condensate should have a vinyl tube dedicated to draining into a laundry sink or a secondary drain, sump pump pit, or even outdoors. Every state is going differ though.
@Jdw6848
Ай бұрын
Before you do anything make sure you have a clean air filter!
@NewHVACGuide
Ай бұрын
Great point. Airflow should always be checked first.
@waltofalltrades6817
Жыл бұрын
I guess my problem is that I live in a tin can (old mobile home) in the south. There's a 21 degree difference between the return air and the cold air coming out the vents. That's with a 93 degree outside temp too.
@rickysanchez5264
2 ай бұрын
No insulation in the attic will cause the unit to turn on and off more frequently
@NewHVACGuide
2 ай бұрын
Certainly will
@richardremmers6969
Жыл бұрын
What's the best tool to check DeltaT?
@rolandberendonck3900
24 күн бұрын
A thermometer
@aubreyalmaguer-bd5nb
Жыл бұрын
are you service in florida
@PeezyReacts
Жыл бұрын
What about hot upstairs and a cool downstairs. I closed downstairs vents to about 20% output to force air upstairs but the system is still not keeping up with the heat. Any suggestions to repair this?
@CaptNemo_
Жыл бұрын
my ac turns on but that thing out side of the house wont turn on and no cold air, i dont want to call a hvac to spend 400$ any help?
@dickhertz8103
Жыл бұрын
change out your capacitor on outside unit. If that don't do it then change out the fan motor.
@lindaruggles
Жыл бұрын
And clean the outside of the condenser coil after you've killed the breaker(all power) to it. I just paid a pro to do that for me and that was the whole problem. Also if the unit is over ten years old, have a pro replace the relay(contactor).@@dickhertz8103
@LubaLuba1
2 ай бұрын
If you're not going to help us with adding refrigerant, then don't put a video out
@YT-User1013
2 ай бұрын
Actually, you have to be a licensed HVAC person to even buy refrigerant let alone add refrigerant! No one is going to sell it to you without a license.
@raymondjmcclain
2 ай бұрын
Most people don't have HVAC equipment for this. Pumps, vacuums, gauges, and tanks with compressed gases. Much more complex than something like replacing a capacitor.