UPDATE: the NH00-fuse has an Icc of 25.000A, not 120.000A as stated in the video. 🎁 Free diagrams: cleversolarpower.com/free-diagrams/ 📖 My best-selling book: cleversolarpower.com/off-grid-solar-power-simplified
@Sydneywizard
9 ай бұрын
Thanks for sharing and educating us with your knowledge. Its much appreciated and Merry Christmas to you.
@cleversolarpower
9 ай бұрын
Thank you! Happy holidays!
@rorymax8233
4 ай бұрын
Interesting and valuable information, thank you.
@davidcromapix9083
5 ай бұрын
Thanks , very useful data.
@magi-jd2ug
Ай бұрын
You better make sure your recommendations are correct, the NH00 fuse from siemens does not have an ICC of 120kA at DC voltage, it's only 25kA. Have a look in the datasheet.
@cleversolarpower
Ай бұрын
Yes indeed, the DC Icc is 25kA. I didn't make the distinction between AC and DC. Thanks for your comment.
@Electronzap
8 ай бұрын
Good info.
@The_Unobtainium
Ай бұрын
This is the best summary in this subject so far! Thank you.
@TexasStatesman
23 күн бұрын
Renogy sells an ANL fuse rated for 72v and provides a spec sheet. I'd be interested in your thoughts on. It is the only ANL fuse I can find rated more than 24v. Thanks for the valuable information.
@cleversolarpower
18 күн бұрын
I've seen littlefuse have 80VDC fuses, you can check it on currentconnected: www.currentconnected.com/product/lynx-cnn-shunt-fuse/
@2hotscottpro
9 ай бұрын
Good info.I was looking to upgrade fuses and battery shut-offs.I have cheap fuse you showed ,top left one showed in group of 4. My positive shut off post gets warm from 800 watts using 1500 watt heater on low.I know heat makes them fall apart.Bussman 187 series push button disconnects are $55.
@cleversolarpower
9 ай бұрын
I recommend using the disconnects switches from bluesea systems. They have less resistance. Read my article on my website about 'how to calculate power loss in a circuit'
@simon359
9 ай бұрын
A lot of the 48 V systems I see use mega fuses, and I didn’t see what you recommended for charge controllers? 48 V system in USA
@cleversolarpower
9 ай бұрын
Some mega fuses are rated for 58V. But people copy from other setups, so they can be faulty. 58V rated mega or midi fuse for charge controllers.
@URackADisciprine
8 ай бұрын
I have found Class-T fuses lower than 100A from Bussman and LittelFuse in my searches. Am looking to get an 80A (something like LittelFuse JLLN080P 80A 200KA) for a 48V LiFePO4 battery but no clue which holders will work with that. Wish they were sold as a pair.
@cleversolarpower
8 ай бұрын
The holders are sold separately. Make sure you got the right one. There are different ones for different currents. I think there are two types sold by bluesea systems.
@URackADisciprine
8 ай бұрын
There are two from Blue Sea systems, they are both too large. One is for 110-200A and the other is from 225-400A. I can't find the one I need which is for 70-100A.
@finleyandtom
7 ай бұрын
Thanks for a super clear and informative video - So i am correct im thinking that with a 12v 105ah lithium battery i would be ok to fuse the main connection from the battery with a suitably sized midi or mega fuse ? 105x10 = 1050 amps max during short - IIC for a midi fuse is 5000A and 2000A for a mega
@cleversolarpower
7 ай бұрын
That is correct.
@TheFlashmark
6 ай бұрын
Why we can't use ANL fuse for 48v LifePO4 batteries pack?
@cleversolarpower
6 ай бұрын
The Icc rating of an ANL fuse is too low.
@ML-hf6ii
3 ай бұрын
@@cleversolarpower why then victron use them? for example they recomend using "Victron ANL 80V 48V"
@deanb949
3 ай бұрын
@@ML-hf6ii I experienced the re-bridging of the fuse element when I used a 80 amp ANL on my 48 volt AGM pack. I had used the ANL as a temporary fuse and it became the permanent. One time my voltage was low on batteries, I plugged into shore/ utility to recharge and that higher than normal current took out the 80 amp ANL, which was still arcing after the main element blew. This video has great info.
@deanb949
28 күн бұрын
@@ML-hf6ii You can trust Victron's product to perform as they specify by way of their reputation. 95% of other ANL fuses are no name copies. I'm sure Victron can elaborate on how their ANL fuse is higher voltage capable.
@ML-hf6ii
27 күн бұрын
@@deanb949 read comment above
@The_Unobtainium
Ай бұрын
Where can you find T-class for $40? I'm just checking T-class JJS-350A/60/V and it is...$250! a piece😢 the fuse blosk itself is $120. So expensive.
@cleversolarpower
Ай бұрын
Try Amazon. You can try nh00 fuses as well, they are close to being the same.
@The_Unobtainium
Ай бұрын
@@cleversolarpower yeah, trying but if you want to go for 200A+ mark for DC the prices are kinda shocking
@laurentsosson1739
3 ай бұрын
Hello and congratulations for the tests with the fuse I would like to ask you something I have a large LFP battery pack (EVE 280K) in 9S 4P or 28 volts 1120AH and my voltage converter is 4000 watts to 28 volts which fuse do you recommend between the + of the converter? 150A? fuse like yours or a fixed fuse like VICTRON? THANKS laurent
@johntheaccountant5594
9 ай бұрын
Why can you not use an MCB instead of a fuse?
@cleversolarpower
9 ай бұрын
An MCB is more expensive than a fuse. MCB's are used in AC switchboards. In a DC circuit the fuse wil seldom trip, so that's why we use a fuse. However, and MCB is used as a disconnect between the solar panels and charge controller.
@johntheaccountant5594
9 ай бұрын
@@cleversolarpower when you were saying "fuse/breaker" is US$15 dollars, I was thinking that an AC MCB is US$6 and doesn't have to be replaced when it activates.
@ZIlberbot
6 ай бұрын
except choosing fuse 10 times more than battery capacity, there should be like a precise formula with battery voltage as well, as energy of short circuit battery or power source is Amperage x Voltage x time ....
@cleversolarpower
6 ай бұрын
It is not the fuse rating. It is the short circuit fuse rating, these two are totally different. As you can see on the table different voltages have different short circuit current.
@SiBex_ovh
4 ай бұрын
If you show a example with Rate Table for ex. Class-T then this video will be perfection.
@caseyl3631
2 ай бұрын
are there resetable fuses / breakers out there that you recommend that can do 300amps or more?
@2hotscottpro
6 ай бұрын
What size fuse for 920ah 48v is why I’m here.
@cleversolarpower
6 ай бұрын
You need to figure out what load you want to power for the fuse size. For the fuse type, you likely need class-t or NH if it's lithium.
@2hotscottpro
6 ай бұрын
@@cleversolarpower 6k watt inverter with Li bat
@fc436
7 ай бұрын
my 100a nh have 120kA at 500v dc icc
@magi-jd2ug
Ай бұрын
What fuse is that exactly? I quite positive that is AC only (120kA ICC).
@npvols4321
6 ай бұрын
Please help, i have a 5000watt inverter, 4 x 200 amp hour AGM batteries , and 4 230 watt panels. I think i need a 400amp Class T fuse, but i dont know where to put it ? 12v system Please advise.
@jamesmason7124
2 ай бұрын
No further than 2 feet from the battery but as close as you can and on the positive cable
@mopikozz
2 ай бұрын
Why do i use some people using DC circuit breaker instead of fuse? Isnt DC breaker better in the sense its not single use?
@cleversolarpower
2 ай бұрын
Normally we use fuses with DC because it's cheaper. And they are not blowing. AC breakers can blow more often so we use breakers.
@ML-hf6ii
3 ай бұрын
there are a lot anl fuses for 48V. Why I can't use them?
@cleversolarpower
3 ай бұрын
You can if they are rated for 58V. Most are not. ICC also plays a role.