Just a heads up, if you look at the marking directly to the right of the 14, 12, and 10 on Table 2 (looks like a little scwiggly mark). You will find directions on the Table 2 concluded page that direct you to rule 14-104, or 14-104(2) specifically that indicate that 12,14 and 10 have different allowable ampacities than what is listed in Table 2. 14= 15A, 12=20A, and 10=30A. Otherwise, great video.
@alyaaismail7359
5 ай бұрын
thanks for this comment!
@munchkineater4226
10 ай бұрын
Hi David thank you for sharing this. May i ask if where do you think i could find more exercises like these even questions for voltage drop and likewise?
@transmisionwebeo1821
9 ай бұрын
If the ambient temperature is 15 degrees Celsius, I don't need to include temperature correcting factor in the calculation?