Also would you know how far apart the smokes need to be? Im in California, anything different i need to do due to the place I’m in?
@kayyatech4580
7 ай бұрын
Depending on the building's layout. A detector should not be more than 6m from any wall or obstruction, and no more than 12m from another detector.
@bitrusdenis2373
6 ай бұрын
Some detectors don't come with the positive and negative terminal names some are numbers, can you tell us how the connections are made with such detectors.
@mychannel8809
3 ай бұрын
The detectors that aren’t marked are not polarity sensitive, as long as your negatives and positives line up it will work wired either way
@MarioHernandez-wj1iv
7 ай бұрын
Where do you put the resistors? Is this similar to most Fire alarms?
@kayyatech4580
7 ай бұрын
As the name suggests EOLR should be installed at the end of a security loop. In most cases, EOLR can be only installed at the end. That is because if it's not, the effectiveness of resistor is lost.
@praveenkonduri1782
4 ай бұрын
Hi bro. Fire damper connection crh. ct1 divice se 4 damper connection explan plz
@mychannel8809
3 ай бұрын
Sounds like a bad connection for a specific device, look at the report it will tell you which device this is and check the wiring