Bryant Furnace parts on amazon→ amzn.to/2wY6FDf
There are several troubleshoots the furnace sticker lists that might be the problem. I point out several of them. If you don't care to learn anything about the furnace and what sets off an error code 33, then just skip to 6:00 to see the fix. But for most people, I think it would be helpful to watch the whole thing, (sure would have saved me a ton of time.) But now I know a lot about furnaces!
#33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open. The blower will run for 4 minutes or until open switch remakes whichever is longer. If longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame Rollout switch and BVSS require manual reset. Check for:
Restricted Vent
Proper Vent Sizing
Loose blower wheel
Excessive wind
Dirty filter or restricted duct system
Defective blower motor or capacitor
Defective switch or connections
Inadequate combustion air supply (flame rollout switch open)
Bryant Heating and Cooling Systems
Natural Gas
Central Furnace
Model Number 310AAV048135 / 310AAV048135ACJA
Manufactured JUL 2006
1/2 HP Motor