Great videos Dana! I haven't come across a video over the condensate pumps. I'm curious what issues you've run into with them and the solutions you've found.
@InverterAlways
2 жыл бұрын
Biggest issues are wiring in the float switches. Check out the video I did on a3 error codes where I go into some of the more common issues and how to properly wire them in.
@Blueblurr112
2 жыл бұрын
Another great video. Thank Dana.
@InverterAlways
2 жыл бұрын
Thank you! Wrapped up editing on episode 14 tonight, got lots in the pipeline!
@jamesxiao815
2 жыл бұрын
Hello Dana Thanks for your great videos Do you know why the vrv 3 system display only h4p solid Thanks again for your hard work
@InverterAlways
2 жыл бұрын
Is it 3 phase or single phase (what's the outdoor model)
@IrfanAhmad-du5nw
2 жыл бұрын
Hi Dana , thanks for your support. Just a question on how to go on the run test mode after replacing the Main control PCB on vrv 3 systems
@InverterAlways
2 жыл бұрын
From h3p only light on hold test button until 2 and 7 come on. That signifies test has started.
@johnnyroxannebautista2063
2 жыл бұрын
Im am going to replace main controll pcb maybe next week for VRV 3. i know i have to copy the dip switch setting on manual, but i wanna ask something that confuses me. Is it necessary to conduct test mode? i mean ,can i just go directly to let the indoor run and set to cool mode waiting for the compressor to kicks in?
@InverterAlways
2 жыл бұрын
@@johnnyroxannebautista2063 you will have to run test operation.
@johnnyroxannebautista2063
2 жыл бұрын
@@InverterAlways thank you. noted on this sir
@gowkarranpooran4771
2 жыл бұрын
My daikin with 4 headers stop working the condenser displays oooo headers are blowing hot air and on/off switch is blinking what should I do there was a storm a week ago and all was working fine your thoughts. Gowkarran
@InverterAlways
2 жыл бұрын
Whats the code on the stat blinking?
@johnnyroxannebautista2063
2 жыл бұрын
Hello Dana / i wanna ask something. I know this is out of topic cause i can't find a video of yours with regards of my concern. Im doing VRV 4 with the thermostat of BRC1C62. But i found out that the fan speed of indoor is Low and High only. L ,H,HH Do you have any idea how to set that?
@InverterAlways
2 жыл бұрын
Usually there is a fan speed button on the controller.
@sergeshevchuk1679
Жыл бұрын
Hey Dana Where are all the videos?
@InverterAlways
Жыл бұрын
I hade to take down my videos I'm sorry
@truthedge5629
5 ай бұрын
HELLO , is this manipulation for the forced fan doable on the VRV III modules ? i have U2 and some times U4 errors .
@InverterAlways
5 ай бұрын
Yes, mode 2 (Service mode) setting 5 on all vrviii and later systems. I'd be willing to bet it's on the really old vrv2 systems as well but those are from before my time so I cannot confirm.
@InverterAlways
5 ай бұрын
Also u2 is power related most of the time. Add a phase monitor icm450 (I think), you want power to get removed for at least a minute any time there are bumps or surges. It acts as a surge protector as well.
@truthedge5629
5 ай бұрын
@@InverterAlways I tried to go forthe forced fans but ... nothing works , with remote on and off both cases doesnt work . even the reset ( bs5 for 20 seconds ) doesnot reset the system , i wanted to reset to link one only interior unit with a new adapted communication wire then try to check for the reason , but it doesnt reset . thank you for the response
@hvacandvrvspecialvedoindus7891
2 жыл бұрын
Very helpful video but hindi language please 🙏😂❤️
@InverterAlways
2 жыл бұрын
That is going to be tough. I will keep it in mind if I ever get someone to translate everything.
@kuldeeprajput7276
2 жыл бұрын
20 sec
@InverterAlways
2 жыл бұрын
Magic number
@alexsparkes3194
2 жыл бұрын
Daikin still using Binary settings the biggest pain in ass 1980s tech
@InverterAlways
2 жыл бұрын
It may be old but it's actually pretty fast once you learn it. And one of the best things about it is being able to change stuff on the fly no power down needed. Other brands are still using dip switches which requires power to the system to be shut off which takes way longer than just simply adjusting a binary setting. Other brands also require laptops to be plugged in to make setting changes while Daikin does not. From a time on the job perspective, at least in my experience, Daikin is way faster with their binary format. And again once you learn how to navigate it, it's quite simple.
@claudioarends2899
4 ай бұрын
Useless as always.
@InverterAlways
4 ай бұрын
Forced fan? It's quite helpful in many situations. What's useless about it?
Пікірлер: 29