I noticed that in all of the examples the heat recovery chiller is not replacing the "regular" chiller. Is the heat recovery chiller able to do that? Basically, can we on demand activate or deactivate the heat recovery feature? Some owners my not like the first cost appearance of 2 chillers AND a heat recovery chiller as opposed to simply having chillers that are able to recover heat when that is needed.
@TECTubefilms
Жыл бұрын
Yes, example #1 around the 20 minute mark has the HR chiller in parallel. That example shows 3 total chillers but you can do the same with 2 chillers... one that is regular and one that is heat reclaim.
@TECTubefilms
Жыл бұрын
No, you do not activate/deactivate the heat recovery functionality because these chillers do not have their condensers piped to the cooling tower. The heat load is their cooling tower. You can only size and run them for your simultaneous heat load during cooling season.
@lasonheng2083
Жыл бұрын
Can you tell me about the component of heat recovery that w need to use with chiiller?