The 75 degree column was used for conductor sizing, the 60 degree column isn’t used even though less than 100 amps , i agree with the 75 degree column just asked in case there was confusion.
@electrical1019
Жыл бұрын
Hi there, we always assume 74 degrees for all motors unless a question/specific motor says we can't, since essentially all motors used today have connections rated for 75 degrees. Hope that helps!
@vrbaac1641
Жыл бұрын
hi, thanks for the video ^^... just want to ask... are these steps applicable to both single and 3-phase motors? thanks ^^
@electrical1019
Жыл бұрын
Yes they are! You will just use slightly different references for a single phase versus a three phase motor (i.e. table 430.248 for single phase motors, table 430.250 for single phase motors etc.). Hope that helps!
@jeisonmercado4720
Жыл бұрын
Hi thanks for this video I wanted to ask if you are able to provide a pdf of these step to paste on the back of the code book?
@electrical1019
Жыл бұрын
Yes, in our video "Graphics for the National Electrical Code" there is a link in the description to download the PDF's and the video provides step by step directions on where to put them in the NEC!
@realsugar69
Жыл бұрын
working with Tom Henry?
@electrical1019
Жыл бұрын
We incorporate a variety of Tom Henry materials while teaching, but we do not directly work with or are affiliated with him.