This is a very helpful & only video on youtube that explains step by step guide for commissioning. I struggled a lot 2 years back to do this. Keep this work going brother, wonderful video. Thanks a lot 🙂🙂
@mohammedbasith8395
2 жыл бұрын
Thanks for creating wonderful video... Your explanation is very clear... Keep it up and All the best 👍💯
@محمدالصعيدي-خ1ت6ت
Жыл бұрын
Does the replacement need to be programmed and is the programming manual through the board or through the computer ?? Please answer me.
@sanjugautam3635
6 ай бұрын
Sir please solve my issue. When I auto learn the panel. Both the loop and the device are visible But only Loop One is visible in the laptop's software. How do I assign loop 2 in this condition? Please reply me what is the problem.
@khue109
4 ай бұрын
Hello, do we need to program the address for detector before programming on the panel? Thank you
@ibrahimsha1992
8 ай бұрын
Great Work. Well Explained....
@mohammedbasith8395
2 жыл бұрын
If u r free...Can you make one video for gst ifp-8 mimic panel programming.
@vijaypalsingh6254
Жыл бұрын
its amzing video and salute
@SelvaKumar-vd1lx
2 жыл бұрын
Hello sir, i need your help to connect 5 control panel. After networking all panels the equation are not functioning. Need your advice
@armanalnasar4121
Ай бұрын
PERFECT EXPLAIN.
@SatishKumar-dt4uw
Жыл бұрын
Sir agar aap is video ko Hindi me bhi voice over kar de to bahut help or behtar hoga samajhne ke liye 🙏
@vishnuvg6548
8 ай бұрын
Hi Sir,am facing one issue,given delay is 60sec,any zone fire Pava Modules need to activate in 60sec,but those modules activates in 30sec,could u plz help on this
@mkb_videos
Жыл бұрын
Great
@bijumonbiju6225
Жыл бұрын
Hello sir I have a doute how to create a equation of adjustion zone activation et zone 1 I have smoke and sounder and zone 2 I have one input moduled and a out put moduled. I need to activate when zone 2 activate zone 1 sounder should activate. Please help me
@shyamsharma8659
Жыл бұрын
wonderful video
@lalitsharma1018
Жыл бұрын
We are facing problem to connect laptop USB port to GST 200N system port. Showing yellow error in device manager. what to do?.
@janiceguadalupe8058
8 ай бұрын
Hi sir. System fault must be reset mannually. That is thee problem of my oanel. What shiuld i do
@nileshpanchal5666
Жыл бұрын
Nice explanation..
@olimohamed1578
2 жыл бұрын
Hi How to auto reset the fire alarm when our panel received the fire alarm signal and if the mall panel is reset our panel also need to reset automatically..how to do it ...
@subhamsingh1696
Жыл бұрын
When I restore back I will backup restore successfully software will be restarted after reopen software restore data not showing what is the reason behind that pls help
@mahalomgirhussin1208
Жыл бұрын
Thank you so much. How to USB driver setup
@RahulSingh-gq3up
6 ай бұрын
"There is no port" Proble showing in software when we click on COM set kindly give any sugestion
@chennakesavarao3997
Жыл бұрын
I have connected PA system in panel.When fire happens pa system not working.
@yogeshdabhi363
9 ай бұрын
Can anyone tell me from where can I buy GST programming tool ?
@Facpinfo
2 жыл бұрын
Can we write the location without pc?
@ronaldsamarista4876
Жыл бұрын
Hi sir im from philipppines can iask where to buy that communicator card/download card?
@saravanamoorthy6892
Жыл бұрын
In Philippines dono... But it is available in chennai - tamilnadu- india, against order
@ananthvenkat2999
Жыл бұрын
Thank you sir....
@safetytechchannel5694
Жыл бұрын
Program card is available?
@shahid8639
5 ай бұрын
Can anyone tell me how to tackle with ground fault in GST200
@safdarhusain5233
2 жыл бұрын
Due to water leakage on 2nd floor, display of GST 200 panel at ground floor is empty, showing nothing any text on display but only light, no 24v power on loop out /loop in point even loop wire disconnected. What will be reason and how to troubleshoot it
@Lowvoltage
2 жыл бұрын
If we confirmed as water entered into the board, first we need to check which part of the board is damaged and then it need to replace. If it is not visible, first we need to check the pins in the power supply board's output voltage and then the pins where these power supply terminals are connected. Mostly, when there is any issue on the main board (the PCB board on the back side of the front door), this display won't come.
@JharGyanDarpan
Жыл бұрын
PART CODE MB-221N. Will hv to replace...Or repair if possible..So maney panel hv same problem, nd I spoke it
@gourabdhara6884
2 жыл бұрын
Sir plz tell me how to disable sounders?? Whenever I'm trying to disable all sounders it is showing on the screen "Please wait". After that disable LED not glowing.
@gourabdhara6884
2 жыл бұрын
I'm speaking of GST-Ifp8 panel disable sounder option
@Lowvoltage
2 жыл бұрын
Press Button 8 (enable/disable) - give password as 11111111 - enter - press 1 for disable device - press 3 for all loop sounders - it will ask the panel address - give the 3 digit panel address - enter. We will get a display as "success" in the panel and disabled and sounder flt/Dis led will glow permanently.
@gourabdhara6884
2 жыл бұрын
Sir I tried by this only. But it is not happening. I can't share you image here. Kindly give me your mail Id Then I can show you how exactly it is happening
@activetechnicalservicesats5184
Жыл бұрын
How to set Address in Devices like 1,2 ,3 etc?
@vijaypalsingh6254
Жыл бұрын
sir zone wise led glow karna plz make on video
@adamskibondo
2 жыл бұрын
Hello boss, I have a GST Jb-gb-gst1500h
@electricalengineerb.b6010
2 жыл бұрын
Sir software kese download hoga
@sagalakalatamizhan4837
Жыл бұрын
Autocheck port successful but uploading device error comes can help me
@yanoosayaa8741
3 ай бұрын
I also have this problem
@mikemakokha8931
2 жыл бұрын
Hi am trying but it's not uploading but it's downloading please help
@sagalakalatamizhan4837
Жыл бұрын
Same problem I am facing can u help
@prajwalshinde5098
6 ай бұрын
Same problem I face can you help please
@cloud30yt
Жыл бұрын
what will happen if it becomes upload error
@yanoosayaa8741
3 ай бұрын
I also have this problem
@viveksharma9088
2 жыл бұрын
how can I use dalay time in this
@Lowvoltage
2 жыл бұрын
When we create the equation, in the effect Device, we have the option to set the Delay Time in seconds.
@starelectroline3960
2 жыл бұрын
Dear Sir please splean GST 200 ADDRESSBLE PANEL COMISSNING AND PROGRAMING Hindi language VIDEO
@srinivasasubramaniyan8117
2 жыл бұрын
Sir how to set equation for main gate sounder as common where other area sounders should work as zone wise sounder
@Lowvoltage
2 жыл бұрын
First, we need to assign this sounder as a seperate zone. Then, along with zone wise equation, we need to create one more equation as (in condition device) "any zone, any device activate - (in effective device) this perticular sounder zone with device type as sounder.
@umarmohammad4166
2 жыл бұрын
respected sir I'm you subscriber please help me I'm leaving Mumbai I want to purchase this card rs232 .how much
@sanjugautam3635
6 ай бұрын
Hi sir
@boxervignesh
Жыл бұрын
How to reset the panel password
@prajapatkamleshact8939
5 ай бұрын
Sir apke contact number mil sakte h kya
@mohammedbasith8395
2 жыл бұрын
If u r free...Can you make one video for gst ifp-8 mimic panel programming.
@shyamsharma8659
Жыл бұрын
Hello sir, i need your help to connect 5 control panel. After networking all panels the equation are not functioning. Need your advice
Пікірлер: 60