Sir mai york chiller pe kaam kr rha hu.pls.sir condenser ka high pressure aur Evaporater ka.high pressure kitna hota hai bta dijiye
@c4chiller9984
Жыл бұрын
dost gas konsi hai apke system me ??
@atayamishra2420
Жыл бұрын
@@c4chiller9984 R134a hai sir
@hvacengineer4842
Жыл бұрын
Solenoid valve ko le kar jitna confusion tha sab dur ho gaya thanks sir great explain
@c4chiller9984
Жыл бұрын
thank you ji 👍
@jollyscaria1922
Жыл бұрын
Liuqed line fixed gas conrolld hevy euqpend cnorll systom conrooled portacting comprssar s portong inside parts portacting val systom not damaged systom meckankprds
@mdnadeemakmal3359
Жыл бұрын
Sir HVAC TECHNICIAN ka Course karne ke liye koi institute ka naam bata dijye plzz
@erpoint2661
7 ай бұрын
You deserve million subscribers
@c4chiller9984
7 ай бұрын
thank you for loving and supportive 👍💐
@Bilal-l1q1r
8 ай бұрын
Solenoid valve or electric expansion valve same hota hai kya🤔
@deepakmalviya2401
5 ай бұрын
Brine chillar ka kuch khowlege mil sakta hai kya sir
@atayamishra2420
Жыл бұрын
Sir pls chiller ki wiring aur thermostat ki wiring ke bare me btaiye
@c4chiller9984
Жыл бұрын
dost uske liye digram ke sath bana ke upload kar denge ...time milega to 👍
@atayamishra2420
Жыл бұрын
@@c4chiller9984 Thank u ❤️ sir.eintjar hai apke video ka.
@pradeeptelhure1614
Жыл бұрын
Sir solenoid valve kaha kaha lagaya jata hai .....kya locations par? Jaise ki compressor ke pass bhi hote hai loading and unloading slider valve ke liye. To vo kaise kam karta hai
@faizalam3016
Жыл бұрын
Ap video shoot india me krate ho ya gulf
@campergameplay8880
Жыл бұрын
Sir ap ka video bahut km ata hai
@c4chiller9984
Жыл бұрын
thank you jii
@TanveerAhmed-fz6gk
Жыл бұрын
Sir cold room ko frizar room mn kesy convert kr sakty hn
@prakashgotame8875
Жыл бұрын
Hello sir chiller me liquid level senser kyu use hota he kya kam karta he sir piz reply
@digital_marketing2022
Жыл бұрын
On solenoid Vulva , you have explained very well, I like it. keep it up. Good
@c4chiller9984
Жыл бұрын
thank you for supporting 👍
@imadmaroofi8910
Жыл бұрын
Sir tou is flow control tou nhi Howa na bss line completely open or close hota hai???
@mdghulammustafa2475
Жыл бұрын
Thermostate ke bare me video bnaiye sir pura detail kya kaam hai aur iska wire kitna mm ka hota hai
@mdshahnawazali1272
10 күн бұрын
Super hit jankari
@IrshadAhmad-eu4cx
Жыл бұрын
Sir please lead and lag k bare me explain kariye
@meratera9418
Жыл бұрын
Sir vav kiya h Kai se kam karta h
@KzyxoyKyto
10 күн бұрын
Thanks
@brightchannel2449
4 ай бұрын
Very very very nice vedio thanks 🙏🙏🙏🙏🙏
@c4chiller9984
4 ай бұрын
Thank you 👍
@Comedy_night008
Жыл бұрын
Aap jaisa explainer mil jaye to kya bat hai sir pura configuration dur ho gaya. Waise 1 q hai sir primrey pump aur secondery pump me kon kon sa valve us hota hai uske bare me thoda bata dete 🌝🌝🌝🌝😳😳
@Jenaofficial2017
Жыл бұрын
Nice explanation bro i appreciate it 👍
@campergameplay8880
Жыл бұрын
Interview me ek question Aya tha compressor ka average kya hai sir iska answer plzzz
@c4chiller9984
Жыл бұрын
ji average ye hota hai ki .. compressor kitne % load pe good performance deta hai ..👉.to jaise ki best compressor average 70 to 90 % load good hota hai compressor ka
@fanterzseditizs1593
Жыл бұрын
#Ask sir kiya Hvac 3 years ka course karne se gulf company main job lag sakhti hai please reply zoror karna love you from Pakistan 🥰❤
@c4chiller9984
Жыл бұрын
ji ha ..aap 3 years ka ache se experience leke Jaa sakte hai ...baki koi question ya doubt ho to any time pooch sakte hai..sukriya 👍😊
@shoebkhan7010
Жыл бұрын
Sir yeh solenoid valve sirf water cooled chiller mein use hota h kya plz sir bataye humein🙏
@c4chiller9984
Жыл бұрын
dost ye water cooled air cooled kahi bhi use kar sakte ho ...jaha iski requirement ho waha pe aap use kar sakte ho ...flow ko rokna hi iska kaam hota hai bas
@sikandaralam2959
Жыл бұрын
I have one question electronics Expansion valve percentage pe open hota hai jab ye close rahega to liquid kaise jayega
@c4chiller9984
Жыл бұрын
jab supply aati hai to ye load ke according open aor close hota hai . percentage ke hisab se hi open hoga ...close tabhi hoga jab supply off hogi ....agar system running hai to ye kuch percent open hi rahega ...chahe low load pe hi q na system chale .....aisa samajlo ji aap ki ye PICV actuator ki tarah kaam karta hai ...jo ahu ke outlet line me use kiya jata hai...👍
@vickydollar2768
Жыл бұрын
Sir ji BMS system fall ho gaya to us condition per kya kare
@vickydollar2768
Жыл бұрын
Manual kase chalayeh plaes is per video banao please sir
@kantilalpatel8196
Жыл бұрын
my compressor get cold , to touch may be this solonoid valve is malfunctioning in manitowoc ice machine , please let me know
@c4chiller9984
Жыл бұрын
your solenoid valve work proper or not ??
@SaddamKhan-wp4om
Жыл бұрын
Good answer bhae. Isi pr kam kar rahe h dx (ac) hai ham log( ahu) pr lagaye h sonlet valve ko...🤝🤝
@c4chiller9984
Жыл бұрын
good 👍
@saddamhaidar786
Жыл бұрын
Thanks
@RPYADAV-st9gm
8 ай бұрын
Bhai ak refrigerator sycel Bana kar dalo aur uska har points par temperature kya hoga gais R134a ka
@c4chiller9984
8 ай бұрын
refrigerator ya refrigeration cycle chaiye dost apko ?
@fanterzseditizs1593
Жыл бұрын
#Ask sir kiya HVAC course karne se chiller Plants k bare main Pata lag jaiye ga ?
@c4chiller9984
Жыл бұрын
ji ha bilkul ... because HVAC ka hi part chiller hai ...jise ham central ac bhi bolte hai
@cricketlover7512
Жыл бұрын
Solenoid valve high load & lo load pe bhi compressor ko trip krta hai n sir Or ye compressor pe laga hota hai n
@c4chiller9984
Жыл бұрын
ji bilkul laga hota ..hai screw compressor ke head pe ... loading and unloading ke liye ..👍
@i.kfactsinhindi5570
Жыл бұрын
Bahot dino baad bro
@c4chiller9984
Жыл бұрын
ji ha ...jaise hi time Mila waise hi upload kiya 😊....time hi nahi mil pa raha hai yaar
@arunchauhan7465
Жыл бұрын
Sir jab gas ki ricoveri kerte hai to chiller me kuch regrigarent liqvid fom me hoga to kya vo bhi recover hota hai ya vo chiller me hi rahta hai
@c4chiller9984
Жыл бұрын
sab recover ho jata hai 👍
@beaware9907
9 ай бұрын
kya hum ye keh sakte hai Solenide Valve actuator ki tarah work krta hai?
@c4chiller9984
9 ай бұрын
Dost....Actuator 3 type ke hote hai Jaise ki koi actuator commond milte hi 100% off ho jayega ya on ho jayega...but Kuch actuator dheere dheere off hote hai aor dheere open hote hai ... 👉 Lekin solenoid valve supply milte hi 100% open ho jayega aor supply na Milne par 100% off ho jata hai ...
@RanjanKumar-uf9md
7 ай бұрын
I thought jarur Bihar se ho Itni deeply Bihari hi samjhte hai 😊
@c4chiller9984
7 ай бұрын
thought thoda wrong ho gaya dost .. mai UP vala hu 🤗...BUt thanks dost fOr supporting and loving 💐👍
@kantilalpatel8196
Жыл бұрын
i don't know , how to check solonoid valve , please let me know
@c4chiller9984
Жыл бұрын
direct give power supply 230 volt of solenoid valve and tuch the tester ( normal tester which I use check current ) of solenoid plunger if tester feel magnet so solenoid is proper if not magnet on plunger after supply so plunger is not proper
@motivationalstatus4750
Жыл бұрын
Sir 650 tr chiller ka suction aur discharge pipe size kya hota hai Aur 500 tr ka suction aur discharge pipe size kya hota hai
@sudeshkumar1933
6 ай бұрын
❤
@sarojmahato9213
Жыл бұрын
Sir HVAC ka course kaha se kare . Aapne kaha se kiya tha
@c4chiller9984
Жыл бұрын
apke near by jaha bhi ho aap waha kar sakte hai...uske baad aap practical ache se knowledge le lijiye
@AfrujAnsary
10 ай бұрын
Good explanation sir ji
@c4chiller9984
10 ай бұрын
Thank you jii 🙏
@deepakmalviya2401
5 ай бұрын
Bms k upar video banaya
@c4chiller9984
5 ай бұрын
ek vidio upload kiya hua hai BMS pe description me link hai aap dekh sakte hai.. .baaki koi question hai to aap bataiye dost 👍
@jai.shree.Ram-sena108
4 ай бұрын
Sol night volve agar karab ho Jai to kiya problem hoga aur kise pata kre ki yah khrab hai
@c4chiller9984
4 ай бұрын
apne system kO oN karo aor apke pass agar electric tester hai to aap solenoid valve ke ooper tester ko tuch karo agar solenoid running hai to magnet banega 👉 aor agar magnet nahi aaya to kahrab hai solenoid
@SaifKhan-jf9io
Жыл бұрын
Very good explain ❤
@ShivanshTyagi-shorts
4 ай бұрын
Very good explanation
@c4chiller9984
4 ай бұрын
thank you dost 👍
@faridakhtar8973
4 ай бұрын
Solenoid valve konsi line me lagate hai?
@c4chiller9984
4 ай бұрын
Liquid line me Jo line condenser aor evaporator ke beech me
@altafsiddiqui3527
Жыл бұрын
Thank you❤ sir
@Mazhar7khan
Жыл бұрын
Video download kiya KZitem me lekin premium requirement bata raha hai 169 rupiya paid karne ke Lia bata raha aisa q
@c4chiller9984
Жыл бұрын
aap kisi app ke through download kar lijiye ...jaise vidmate apo
@Mazhar7khan
Жыл бұрын
@@c4chiller9984 Saudi me free download nahi hai snap tube se kiya ho Gaya
@saifushaikh5719
Жыл бұрын
Nice voice brother 😊
@c4chiller9984
Жыл бұрын
thank you 👍😋
@rajkumarchauhan9191
6 ай бұрын
Informative video thank you🙏🙏🙏
@ajazahmad5238
Жыл бұрын
Sir tik tik awaj q aata Hain sir batao na
@c4chiller9984
Жыл бұрын
Tik tik awaj kaise dost ??
@animalslover7132
Жыл бұрын
Sir what is different between cooling type air cooled chiller and heating & cooling type air cooled chiller Please make a video.how to know air cooled chiller is only for cooling aur heating also.
@qaswa2023
Жыл бұрын
Delta pressure increased what happened in chiller condenser subcooling and superheat
@dawoodhussain7633
3 ай бұрын
Good job sir bohat acha
@c4chiller9984
3 ай бұрын
👍👍
@mirzasaidul1948
Жыл бұрын
Thank you sir app aise he Support karta rahiya ham sab logo ko bohot bohot Shukriya sir
@anwarulhaque7881
Жыл бұрын
Thanks sir your efforts too much helpful for everyone
@qaswa2023
Жыл бұрын
Delta pressure increased what happened in chiller evaporater superheat
@mohammedbilal1650
7 ай бұрын
Bhai aap kider kaam karte hai
@c4chiller9984
7 ай бұрын
haryana
@santoshiocl2
Жыл бұрын
Great zob sir
@sankargouda1639
Жыл бұрын
Solenoid check kese kare
@c4chiller9984
Жыл бұрын
power supply do 230 volt ki aor solenoid ke upar jo plunjer hai waha pe tester lagaoge to wo magnet banega ....👉agar magnet bana to solenoid sahi hai ....magnet nhi bana to ... solenoid fault hai
@TanveerAhmed-fz6gk
Жыл бұрын
Very helpful video sir thenks
@babuboda431
Жыл бұрын
Thank u sir nice experience and explain thank u so mach sir
@allahwatchingme3980
Жыл бұрын
Sir ap kam kaha sikhe the??
@c4chiller9984
Жыл бұрын
apne ..india me hi 🤗👍
@atayamishra2420
Жыл бұрын
Very nice sir.apke new video ka eintjar tha.mai apka hi video dekh kr kuwait aa gya interview clear krke
@c4chiller9984
Жыл бұрын
congratulations 🤗💐💐
@atayamishra2420
Жыл бұрын
@@c4chiller9984 Thank u ❤️ sir.apke video se bahut achha knowledge milta h
@MS.0124
Жыл бұрын
Aap kaha work karte hai
@c4chiller9984
Жыл бұрын
india ✨
@mohammadjalaluddin6933
Жыл бұрын
Good explanation
@c4chiller9984
Жыл бұрын
thank you
@abubashar5000
Жыл бұрын
COOLING TOWER KA CALCULATION KAISE NIKAALTE H KI AGAR MERA 400TR KA CENTRIFUGAL CHILLER HAI TO COOLING TOWER KITNE TR KA HOGA ISKA KUCH CALCULATION HAI TO PLEASE ISPE KOI VIDEO BANAYE
@abubashar5000
Жыл бұрын
MAINE APKA 2 CLIP DEKHA THA JISPE AP APNE CHILLER KI CAPACITY 65O TR BTA RHE THE OR DUSRI VIDEO MEIN APNI COOLING TOWER KI CAPACITY 818 TR BTA RHE THE TO ISKA KYA CALCULATION H APKA JO BHI VIDEO AATA H BAHUT HEE ACCHE WAY MEIN AP SAMJHATE HO SO AGAR ISPE KOI VIDEO BANA DE
@abubashar5000
Жыл бұрын
OR AGAR APKA KOI MAIL ID H TO WO PROVIDE KARE JISME HUM KUCH VIDEO KE LIYE APSE REQUEST KARE TO AP USPE KUCH VIDEO BANAYE
@c4chiller9984
Жыл бұрын
dost ek simple formula use hota hai....ki chiller ki capecity jitni bhi ho ....apko cooling tower usse 20 % extra capecity ka lagana padega ... jaise ki chiller capecity 500 tr so . cooling tower capecity 600 tr hona chaiyye jiise ki performance good hoti hai .....
@junaidmansoorijunaidmansoo193
4 ай бұрын
Very nice good
@c4chiller9984
4 ай бұрын
thank you👍👍
@AbdulKhan-u9g
Жыл бұрын
Sir isme konsa type ka expansion valve use hai
@c4chiller9984
Жыл бұрын
dost .... electronic expection valve used hai isme
@AbdulKhan-u9g
Жыл бұрын
@@c4chiller9984 thnk ew sir
@nizamhaiderkhan4949
Жыл бұрын
Thanks for explanation sir
@danishabbasi3485
Жыл бұрын
thank you So much
@c4chiller9984
Жыл бұрын
👍👍
@asifzikriwala1232
Ай бұрын
Thanku bro
@c4chiller9984
Ай бұрын
👍👍
@mohammadkhurshidalam8490
Жыл бұрын
Kaha lagta h sir suction y discharge line me
@c4chiller9984
Жыл бұрын
ye evaporater se pahle lagaya jata hai ...
@c4chiller9984
Жыл бұрын
yani ki liqvid line me
@ramlalitkumar3085
6 ай бұрын
Chhillar waiting ko bataiye sir ji
@c4chiller9984
6 ай бұрын
Chiller waiting....ya chiller wiring dost ?
@ramlalitkumar3085
6 ай бұрын
@@c4chiller9984 wairing
@intakhabalam3377
Жыл бұрын
Very good explain
@mohitverma5613
11 ай бұрын
Very nice explain sir🌹🌹
@AsrafulIslam11789
5 ай бұрын
Alhamdulillah Perfect information my brother ❤❤
@c4chiller9984
5 ай бұрын
thank you dost 👍
@motivationalstatus4750
Жыл бұрын
Dubai ke liye HVAC TECHNICIAN ka aaya hai sir oil gas company ka hai ye isme kya karna padta hai please help me sir kal interview hai sir
@c4chiller9984
Жыл бұрын
dost ....😊 kuch khas nahi ..agar apne kaam kiya hua hai to apko koi bhi problem nahi hogi ...chahe wo oil gas ho ya chemical factory...apko havc ke hi unit milenge jispe apko work karna rahega ....aor achi baat ye hoti hai ki ...apko full shefty ke sath kaam karna hota hai ...yani ki behtar tools ke sath 👍....isliye ap haste hue jaiye ...😊👍
@motivationalstatus4750
Жыл бұрын
@@c4chiller9984 ok sir thanks ♥️ aapne Mera hausla badaya
@c4chiller9984
Жыл бұрын
khud pe believe aor apne work se mohabbat karna dost .... always success rahoge 😊👍
@motivationalstatus4750
Жыл бұрын
@@c4chiller9984 ji bade bhai
@c4chiller9984
Жыл бұрын
aor agar koi bhi doubts aay to ..yaar ham to yahi hai😊 ...kabhi bhi poocho aap log ...jo hame knowledge rahega waha Tak to bata hi sakte hai 😊👍...
@MdAlam-tm8oj
Жыл бұрын
Sir mai aap bhut din pahle bola tha ki.. Ek video banaye... Compressor kaise chenge karte hai.... But aap ne abhi tak nhi bnaya video
@c4chiller9984
Жыл бұрын
dost jab compressor change karenge to jarur ham ...uski vidio banayeneg .. practical..abhi koi compressor change nahi ho raha hai
@sohagmostofa5674
8 ай бұрын
❤
@c4chiller9984
8 ай бұрын
😊💐💐
@habiburrahmanmurat4556
Жыл бұрын
Give video every day. From Bangladesh with love ❤️❤️
@c4chiller9984
Жыл бұрын
ji jarur ....jaise hi time milta hai ham upload karte hai ..and thanks for loving 🤗 supporting ✊
@sarfarozansari4330
9 ай бұрын
Same same actuator..??
@c4chiller9984
9 ай бұрын
yes bol sakte hai 👍
@sarfarozansari4330
9 ай бұрын
Thank bhai 🙏
@shaffiullahshabbushaffisha1231
Жыл бұрын
Very nice 👌 👍
@sachinthakur-pg6ig
Жыл бұрын
Where is it installed??? Before expansion device
@c4chiller9984
Жыл бұрын
yes 👍
@jis8718
Жыл бұрын
Krishcool ka glycol compressor hai jo br br very low suction pr trip krta hai sir plss help me
@c4chiller9984
Жыл бұрын
ji usme ...glycol hai ya phir gas bhi use ho rahi hai
@jis8718
Жыл бұрын
Ji sir pr vhi problem br br aa rha hai jisse tem.nhi ata hai kya problem hai sir isme very low suction ata hai alarm
@jis8718
Жыл бұрын
@@c4chiller9984 2hai gas glycol
@c4chiller9984
Жыл бұрын
us compressor me gas konsi hai??
@jis8718
Жыл бұрын
@@c4chiller9984 R 134 a
@faizalam3016
Жыл бұрын
Thanks
@ghalibansari1690
Жыл бұрын
Really guru ji your technical teaching way too much good
@c4chiller9984
Жыл бұрын
sukriya apka 👍👍
@redwond88did95
Жыл бұрын
Jabarjast very nice 👍 aysa explen koi nhi kerpata thank.s sir
@c4chiller9984
Жыл бұрын
thank you very much 👍
@WORLD_HVAC_SYSTEM
Жыл бұрын
Bahut din se intjar kar raha tha sir 😘🥰💗
@c4chiller9984
Жыл бұрын
acha ji ..🤗👍
@mohammedsalman3225
Жыл бұрын
Thank u sir Jo doubt tha solenoid valve ko leke o khatam ho gaya
@c4chiller9984
Жыл бұрын
good 👍
@a.jansari5341
Жыл бұрын
Bahot hi easy way me samjhaye,aaj tk difficult lag raha tha 👍
@c4chiller9984
Жыл бұрын
apko samjh me aa gaya ...hamari mehnat vasool ho gai 🤗🤗 thank you 👍
@hazeekabdeen7876
Жыл бұрын
Masha Allah good 👍👍👍👍 explain 😊😊😊😊
@c4chiller9984
Жыл бұрын
sukriya ji
@imranaadil7377
8 ай бұрын
Thanks sir jiii sara information diya hai ❤❤❤❤
@c4chiller9984
8 ай бұрын
💐💐💐😊
@Itz____nda____student
9 ай бұрын
Very nice explanation sir ❤❤
@c4chiller9984
9 ай бұрын
thank you 👍
@deepakjadhav7758
Жыл бұрын
It looks it is only use for open and closed purposes , how valve control the flow partially ..
@c4chiller9984
Жыл бұрын
it work direct....100% open or 100% close
@asadhashmi6554
9 ай бұрын
May be partial flow isn't required here. This is a digital type automation( 0,1; either off or on only). If you want partial, then you have required analogue automation.