We piped in a VXT-24 using the Kendorf / SuperStrut fixture and a combination of IP (iron pipe threads), ProPress and sweat fittings and valves.
We had a leak on the new brass fittings.
We used a MegaPress fitting to replace a partly clogged & failing section of steel wet return.
The old threaded steel end of the wet return likely failed & clogged due to galvanic corrosion when copper was tied in to the steel 20+ years ago.
We set the return up so a that "no return" flush could be done while water is added to the boiler.
Removing that old oil tank sure freed up a lot of real-estate!