You should do more of these. I’m at a hotel in Paris and the AC was like barely working. Found this and now I’m nice and chilly ;)
@FullyAirconditioned
2 жыл бұрын
Thanks for the reply, glad to help.
@anisouldhajjaj2326
Жыл бұрын
Hello and thank you for this helpful video. I have the same controller and i wonder how to determine the right setting for static pressure ? F-H, V-H, F-L or V-L
@richardc1983
Жыл бұрын
Which one do you prefer this or the premt premium touch screen? Fyi - over heat and overcool step 0 is 0.5c deadband control on ducted units. (Over in UK anyway) so tighter control than 1c on step 3.
@josephraji
4 жыл бұрын
Thank you ,good job Appreciated 👍
@kristyfenn5216
3 жыл бұрын
Bloody helpful! Thanks for this.
@sn.5755
3 ай бұрын
I have a ducted system and a separate system for family room. The family I can go and adjust esp fan speeds. In ducted I change the speeds but it doesn’t change anything when running. The downstairs is very cold. Trying to increase fan speeds. Help would be appreciated
@barcatv6482
4 жыл бұрын
hello dear can i addressing indoor by thermostat i wanna to be smart but firt need addressing by thermostat indoor this function do or not ? plz
@arson114
Жыл бұрын
Anyone know what voltage I should be getting at the controller? It's labeled as 12v on the back of the controller, but I'm getting 24v. Having problems with all the controllers I've tried and wondering if voltage is the reason. ODU: LG Multi V S. IDU: ARNU363NJA4.
@jasminebower2305
3 жыл бұрын
Thanks for liking my comment! Quick question: every time I try change the temperature on this thing it says "unoccupancy status. Can't set an item". I must have somehow set the place as unoccupied but I cannot figure how to change that 😭😭
@FullyAirconditioned
3 жыл бұрын
Hi Jasmine, Sorry I don’t know, haven’t seen that on a controller before, what type of unit is it (ducted, split, VRF, multi split) if its a VRF and you in an apartment or office building it maybe under centralised control. Do you know who put it in, is there a local LG repairer in the area. Have you tried the trusty reset, turn the power off at the switch board for the air conditioning system for 5 minutes and restart. Kind Regards Craig hewitt
@menosobota552
4 жыл бұрын
Cable long? Thx.
@ronm9367
2 жыл бұрын
I am having issues with the overheating. The heating always shuts off 2 degrees past the setpoint. It starts with 1 degree below the setpoint. I have overhearing at step3. Any insight?
@FullyAirconditioned
2 жыл бұрын
With the LG units they have a different heating / cooling control strategy on the t-stat compared to most other brands. Most other brand have the set-point as the off point (stops heating or cooling) and the on point is in heating is about 1-2k below this. In cooling the on point is 1-2k above the set point. LG’s spin on this is different, the set point is the on point (starts heating or cooling) the off point is 1-2k above for heating or below for cooling. If you set the over heating, over cooling to steps 3 it reduces the proportional band to its lowest amount, should be 1-2k. Also if you set the mode to auto it will act differently again and give a slight different control strategy. Make sure it’s set to sensor active from the wall controller (remo) and not the (indoor) or (2-th). Make sure wall controller is in a good location for measuring the room temp or at least the return air path to give the best average temp.
@darylmorse
4 жыл бұрын
Is there any documentation on the overheat and overcool settings? My thermostats have this, but none of the manuals say anything about how to set them.
@FullyAirconditioned
4 жыл бұрын
Daryl Morse poster a photo in community for the field settings
@TraceeOkrainec
4 ай бұрын
I cannot get the fan to turn off when the cooling isn't happening - I changed the "continuous fan setting" to clear, but it still blows air 24/7 - help?
@FullyAirconditioned
4 ай бұрын
Setting 35-01 will set the fan to cycle with the t-stat, only running when cooling, not possible to be set on 3hp units.
@jasminebower2305
3 жыл бұрын
Thanks! I'm renting an apartment with one of these and It's the most unintuitive, frustrating device ever
@brianwolthers2762
Жыл бұрын
totally agree. Must have been programmed by a school student doing work experience.
@OgnjenGrkinic
Жыл бұрын
Hello, In the lab, we have two LG air conditioners, one of which is smart and the other is not. We are wondering if we could use the LG PREMTB100 Wired Remote Control to connect both air conditioners to it (smart wirelessly and the other one through a wire, for example) and at the same time be able to adjust the air parameters on both air conditioners? If not that, is there any device that would solve that problem? The most important thing for us is the reading of air humidity and temperature. Thanks in advance.
@FullyAirconditioned
Жыл бұрын
One controller can run two units and but it will set each to the same set point and fan speed, you could just install two controllers, one on each system ??
@beoogy
Жыл бұрын
@@FullyAirconditionedyes it's OK to set them to the same values. Great. Do we need something else or just the Controller?
@FullyAirconditioned
Жыл бұрын
You will need group cable for this to work, LG part No: PZCWRG3
@beoogy
Жыл бұрын
@@FullyAirconditioned thank you very much for your quick and helpful answers. All the best!
@dianec2749
6 ай бұрын
is there a way i can dim the panel light for energy saving it stays on all day & night very bright panel
@demolution325
5 ай бұрын
Menu -> Settiings -> User - look for Backlight Dimming Brightness and adjust it accordingly
@dragonling748
4 жыл бұрын
So I've got one of these with Wifi, but that the only bit I can't work out. How do you connect them to the wifi?
@FullyAirconditioned
3 жыл бұрын
I will try and do a video as it's not easy, but you need to put it in to AP mode so it can be found on your wifi network, download the LG ThinQ app I believe it has steps in the app on how to connect with in the app
@djfabiannmusic
4 жыл бұрын
I have just Heat and Auto in the menu! There aren’t other Options! Why? Help me please
@FullyAirconditioned
4 жыл бұрын
Possibly connected to a VRF system and your controller is not the master. What Thor of system is it.
@georgegr8278
3 жыл бұрын
did you fixed it? i have the same problem
@rcprod9631
Жыл бұрын
Does this controller have a touchscreen?
@FullyAirconditioned
Жыл бұрын
This one is not touch screen, it’s touch panel, there is a touchscreen available PREMTB000
@rcprod9631
Жыл бұрын
@@FullyAirconditioned Thank you.
@rcprod9631
Жыл бұрын
@@FullyAirconditionedDo you recommend paying extra for the touchscreen controller?
@FullyAirconditioned
Жыл бұрын
@@rcprod9631 both controller use the same platform one is just touch screen, it’s a personal choice
@zamathutaafonsomanene8371
4 жыл бұрын
Bonjour ! ce bien fait est ce je peux trouver un lien en français svp
@FullyAirconditioned
4 жыл бұрын
Sorry, don't know of one in French
@thaobanhcheud2640
4 жыл бұрын
Bonjour il y a un tuto sur ce lien si cela peut vous aider : kzitem.info/news/bejne/q4KosKCge6F5qW0
@fanasonyc
Ай бұрын
Mine does not work at all it’s an awful system I must say
@FullyAirconditioned
Ай бұрын
@@fanasonyc most problems with air conditioner are installation issues, incorrect size, incorrectly installed and the end user blames the manufacturer. When more often than not it’s the people who installed it that have caused the problems.