Back in the days when I lived on the Canadian west coast, I loved those massive wind storms and power outages. There was something so exhilarating about watching out the window as trees blow apart and power lines explode. Thanks for making these videos, I have really learned a lot from them.
@nics-systems-electric
10 ай бұрын
Couldn't agree more
@petra7306
3 ай бұрын
i love. The way you tern the generator
@adventuresquadofficial
2 ай бұрын
?
@dutchwolf2675
9 ай бұрын
Great video! Activate the bathroom heat detector in the shed and the garage heat in the house. Keep up the good work!
@petra7306
2 ай бұрын
i love how you. Tern. The generator on
@matthewantonucci6751
10 ай бұрын
Hey Nic, The Annunciator For The Notifier System When In Supervisory Beep's Just Like ANapco RP1CAE2!
@gameranoniem3872
10 ай бұрын
next time activate the fire alarm with the pullstation above the fire extinguisher
@igggames819
10 ай бұрын
I would like to see you use smart lighting and try to integrate them into your fire alarm system using sound detection or other methods.
@nics-systems-electric
10 ай бұрын
If someone was to send me Smart lighting I would try for fun but i'm not aware of any functional uses
@igggames819
10 ай бұрын
try smart home solver i think their was a video of him reacting to peoples smart homes and one of them was about fire alarms and RGB led bulbs@@nics-systems-electric. if I had more smart sockets and fans I could set up a fire alarm presurization system.
@Open-Tech
10 ай бұрын
You should smoke out one of the bedroom, smoke detectors, in the next test
@nics-systems-electric
10 ай бұрын
I do like that idea
@TheLastWolfBane
10 ай бұрын
I can't wait for whats next... also I think it's blimey genius to use a power outage detector as a cheap alternative🤯
@Open-Tech
10 ай бұрын
You should test all the smoke detectors on both systems in one video
@nics-systems-electric
10 ай бұрын
Would take way too long that gets done annually
@EASsirenVids01
10 ай бұрын
For next month for the garage system you should do that detector I saw on the flangeless base in the storage room below the rack a tiers sign, and house system you should do the heat detector in the house’s garage
@Random_Emergency_Light
10 ай бұрын
Nice! Feels like the October test was yesterday ngl!
@nics-systems-electric
10 ай бұрын
Yeah I feel like that every month lol
@achannelwithnopurpose1977
10 ай бұрын
I know the system was just expanded, but why not add additional remote strobes in areas that need additional strobe cover but have ample sound coverage. Would allow you to have coverage while keeping everything 15cd. You can also include a blue strobe right outside the front door to satisfy that requirement about a strobe marking where the annunciator is.
@nics-systems-electric
10 ай бұрын
Because it's not a requirement when the systems not required to be there there are no strobes required in any house no matter when it was built however each bedroom is supposed to have a sound producing alarm no point of having a blue strobe for an annunciator when the fire department won't be responding anyway
@achannelwithnopurpose1977
10 ай бұрын
@@nics-systems-electric thought it would be a good idea on the grounds of code compliance considering the system is meant to be protecting something.
@nics-systems-electric
10 ай бұрын
@@achannelwithnopurpose1977 considering fire alarm devices can look out of place in a residential application it would be difficult to place more visual devices where it is aesthetically pleasing especially when it's not a public building where you won't have occupants that can't hear
@the_1drummajor
10 ай бұрын
Ditto if anyone else says but if you filmed at 60 FPS instead of 30 you'd have a better chance of capturing the strobe. Sure would love to have a tower at my place too!
@nics-systems-electric
10 ай бұрын
It does help but then I can't switch lenses while recording
@Mr.WonderfulGaming
10 ай бұрын
Nice Test!
@leafmk
10 ай бұрын
I love your monthly tests, Nic!
@kennedyfiresecurityandelev7771
10 ай бұрын
Anyone notice the other low frequency sounder he added in the bederoom where the panel is?
@nics-systems-electric
10 ай бұрын
0:35
@21volts_gaming_official
10 ай бұрын
Do you think you would expand the sprinkler system to the shed if it would make it safer?
@nics-systems-electric
10 ай бұрын
No because it would have to be buried underground and the buildings not heated so it would freeze
@Dawezil
10 ай бұрын
THIS is the man that inspired me to take up this stuff. Luv your vids very much! Keep it up!
@Dawezil
10 ай бұрын
Sorry about the caps it won't let me fix it.
@SodiumInduction-hv
10 ай бұрын
wow! that’s very cool!
@EASsirenVids01
10 ай бұрын
Just came from trying to install my annunciator, oh my god how do you do this stuff I’m having so much dang trouble with wire lmao
@giamansd712
10 ай бұрын
suggestion for next test: for the house system: duct detector and for the garage system: pull station in the cupboard aka where the attic entrance is and where the ups for access control is
@Dilsonalarmsandelectrics
9 ай бұрын
Can we do a pull station in the storage room in the garage?
@nics-systems-electric
9 ай бұрын
Maybe
@roberthowell5691
10 ай бұрын
You should make it where the emergency lights automatically turn on if the fire alarm goes off
@nics-systems-electric
10 ай бұрын
You would need a whole bunch of different relays tied in to every circuit that emergency lights are on so it wouldn't be practical
@petra7306
3 ай бұрын
i like the clicking
@petra7306
3 ай бұрын
❤❤❤
@demontejohnson2912
9 ай бұрын
Have you tried running both systems at the same time?
@nics-systems-electric
9 ай бұрын
It won't do anything special
@rianflynn2765
10 ай бұрын
Can you also add co alarm to house fire alarm system.
@dutchwolf2675
10 ай бұрын
He has no natural gas supply so he doesn’t need
@HenBasketFireAlarms
10 ай бұрын
There are no gas burning appliances in his house, so no CO detection is required
@Huey-Gamer
10 ай бұрын
I see you added a new strobe near the panel
@nics-systems-electric
10 ай бұрын
0:35
@bigcactus4497
10 ай бұрын
I enjoy the video 👍
@rianflynn2765
10 ай бұрын
Can add hvac shutdown to your heatpump in the garage please.
@nics-systems-electric
10 ай бұрын
No
@onefastslimjim
10 ай бұрын
@@nics-systems-electric🗿
@stillthakoolest
10 ай бұрын
Im guessing he can just doesnt want to
@nics-systems-electric
10 ай бұрын
@@stillthakoolest not really there is no low-voltage contacts to shut it down so it would have to be a contactor which would require cable ran to and installed in difficult locations not to mention there is absolutely no reason to shut it down when it is not serving more than one fire zone it is getting its return air and supplier in the same area
@Dilsonalarmsandelectrics
9 ай бұрын
Can we do pull station at the front door in the house pls
@lutinoflake5115
10 ай бұрын
You have more spots in the access control system right? Why dont You put a reader for the garage door? That would be cool.
@nics-systems-electric
10 ай бұрын
If the garage door had contacts that could be used to open it and close it however it does not
@stillthakoolest
10 ай бұрын
Do you test your GFCI'S Monthly per the manufacturers specs? I test them along with my fire/co alarms monthly.
@nics-systems-electric
10 ай бұрын
No I do not nor do I test breakers
@Williams_elektronik
9 ай бұрын
Can you turn on the fire alarm and when the fire alarm is running you switch to generator
@nics-systems-electric
9 ай бұрын
You could nothing would happen it would only go into trouble during the 18 second switchover
@kyleviolette8808
10 ай бұрын
Hello what do you think the best panel you have is?
@nics-systems-electric
10 ай бұрын
NFS-320c
@zacharystrasser8138
10 ай бұрын
Morning
@ThePurpleMoonZ
9 ай бұрын
Why is no-one talking about the rat in the tower😅🐀🐀
@ethandoesthingslol
9 ай бұрын
@nics-system-electric next test you should try and get a UK fire alarm ;)
@nics-systems-electric
9 ай бұрын
I can't use them on either of my systems
@ethandoesthingslol
9 ай бұрын
@@nics-systems-electric i was just thinking for like a video idea but alr
@nics-systems-electric
9 ай бұрын
@@ethandoesthingslol if I had any but I don't
@nathandoesstuffyt
10 ай бұрын
Is the co detector wired into the fire alarm system?
@TheMcGeeTwins
9 ай бұрын
Are you going to try Wheelock and Eaton Eluxa led fire alarms?
@nics-systems-electric
9 ай бұрын
I do have some wheelock LED strobes but I'm not a huge fan of them I prefer system sensor products
@TheMcGeeTwins
9 ай бұрын
System Sensor is pretty good but I am used to Wheelock because they use it in my school District
@tux7k
8 ай бұрын
Do you have a weather station?
@nics-systems-electric
8 ай бұрын
No I don't
@tux7k
8 ай бұрын
You have some really good height on that wood tower to set one up@@nics-systems-electric
@matthewphelan9288
2 ай бұрын
1:17 jaxson so mad
@nathandoesstuffyt
10 ай бұрын
"only thirteen hundred bucks per testing unit" 🤣
@petra7306
2 ай бұрын
Do the smoke alarm
@enricodigi
10 ай бұрын
Next time could you activate the generator smoke please
@matthewphelan9288
2 ай бұрын
there arw two different types of dogs hearing the fire alarm or a smoke alarm ayla (very calm): ☺️☺️☺️☺️ jaxson(the omg i hate loud noises ones): 👿👿👿👹👿😡😤🤬😖😠🗯️
@adventuresquadofficial
2 ай бұрын
What is the model of the annunciator
@nics-systems-electric
2 ай бұрын
ACM 24-AT
@adventuresquadofficial
2 ай бұрын
Is that the one at the front of the door
@nics-systems-electric
2 ай бұрын
@@adventuresquadofficial yup
@user-zr5qg3ui6x
10 ай бұрын
Smoke alarm
@rodgodx345
10 ай бұрын
U installed a sounder in ur bedroom? Looks cheesy
@nics-systems-electric
10 ай бұрын
Each bedroom
@ETyt6
10 ай бұрын
First
@randomvideo9551
10 ай бұрын
You need an eBay account
@Dawezil
10 ай бұрын
Why would he? He isn't selling anything, plus rather have branded from where he gets an then from risky e-bay.
@Im_even_more_pikmin
10 ай бұрын
I saw 3 new devices
@petra7306
2 ай бұрын
P
@lorgzkouns4410
10 ай бұрын
Next fire alarm test first house pull station than garage fire alarm smoke detector in the bathroom or I say washroom Ps I’m in USA we call bathroom @nics-systems-electeir