How can we control this invertor from CNC controller (Arduino Based) . I tried various wiring but it does not work properly. I want VFD to start/stop from CNC. What is the wiring and parameters for that setup
@huanyanginverter6516
Жыл бұрын
F0.04 = 1 short-circuit X1 and com ,then the inverter starts running
@agroprom9751
Жыл бұрын
why is it written in the instructions that it can be set in the settings of 900kW and 2000A? with all motors this inverter generates error E.oC3. Bad inverter at 2.2kwt
@huanyanginverter6516
Жыл бұрын
Fault, take a video and send it to me
@eugenrudel1975
9 ай бұрын
Hi, Thank you this. Is there also a pdf manuell for the inverter ?
@huanyanginverter6516
9 ай бұрын
yes Tell me email
@eugenrudel1975
9 ай бұрын
@@huanyanginverter6516 what is your email adress. i cant write private messages to you
@huanyanginverter6516
9 ай бұрын
How can I send it to you
@XVladimir
2 жыл бұрын
Good afternoon, what is the difference between COM black and white?
@huanyanginverter6516
2 жыл бұрын
no difference. Are the same
@XVladimir
2 жыл бұрын
@@huanyanginverter6516 good afternoon, what to write in F6.01 so that the current is displayed, not Hz
@huanyanginverter6516
2 жыл бұрын
@@XVladimir Repeat key shift Different information can be displayed
@XVladimir
2 жыл бұрын
@@huanyanginverter6516 point in the instruction F6.01 what to change in it so that the display shows current during operation. When the inverter is running, the parameter display is limited to F6.01, that is, 16-bit binary string, if the bit is 1, the parameters corresponding to the bit can be viewed by the SHIFT key during operation. If a bit is 0, the parameters corresponding to that bit will not be displayed. To set the function code F6.0l, the binary number must be converted to hexadecimal number, and then enter the function code. BIT 4: Output current
@hafizipudzi7595
3 жыл бұрын
Hai, how to contact huangyang customer service? Need to ask the proper way to wiring protection circuit that have rcb & mccb and the amp rating
Пікірлер: 16