Need to emphasize the importance of closing the generator circuit breaker within 5 degrees or less at synchronization. Also to close the generator circuit breaker with the sync scope traveling in the fast direction. Does the generator's circuit breaker control scheme incorporate a 25 relay to protect the generator from closing in out of phase?
@ladysmithrose
2 жыл бұрын
you can close in the slow direction, as long as you immediately increase it once the breaker is closed so you don't trip on reverse current protective relays.
@cees1rijp