I really wish more residential equipment had adjustable txv’s.
@deseani1
3 жыл бұрын
They do from my knowledge. But it's not a need to adjust them
@DanO181919
5 жыл бұрын
I love how you look at the BIG picture. You are a very humble person and I admire that. Also, I like how you show the whole process in your videos. Keep the videos coming they are kick ass!!
@HVACRVIDEOS
5 жыл бұрын
thanks bud, I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@potienkalala5113
Жыл бұрын
I like this video and explains
@TH-ji1ed
5 жыл бұрын
“I’ve confirmed that the thermostat is working even though I don’t like that style it’s a piece of junk”...I’ve been there lol
@jonathankipps9061
5 жыл бұрын
I'm a newbie at this, so confirm if I'm thinking this through correctly. The flashing sight glass was because the faulty expansion valve was flooding the evaporator and suction line with liquid refrigerant. With too much refrigerant now on the suction side, the liquid line receiver ran low on refrigerant. Is this correct?
@joshuapellerito1341
5 жыл бұрын
That is correct. Most freezer TXVs are pressure limiting, so as the evaporator is flooded and the liquid refrigerant is flooding back to the compressor, it fills the suction line with refrigerant causing the system to appear long on charge when in fact its perfectly fine.
@kingsolo6241
4 жыл бұрын
Sun ding liquid through the headers or scrolls can ruin a compressor as well. You want 100% gas going back through the compressor discharge. That’s why we take subcool and super-heat. Same goes the other way. If we have a sub-cool that is off with a flashing sight glass we are ruining the TXV since the TXV needs 100% liquid to work correctly. When gas goes though the TXV the valve body will jump more than needed to. It can destroy the TXV. Especially the way they are made these days.
@JuanTodoli
5 жыл бұрын
TXV all the way in, all the way out, and back to the middle. Excellent procedure to (try to) clear the valve.👍
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@RobRocker09
4 ай бұрын
Absolutely awesome videos and recaps. I been in the residential AC 5yrs When I worked with my old boss we did single evp and condensers. Recently got a lead to go see a customer. He had a parallel Hussmann cabinet. The guy who worked on it move so he says. Had 4 compressors. 1999. Only one compressor was working, he wanted a new and wanted to replace one compressor, 3 were bad. Customer gave me a hard time about adding freon, 55lb system 404A. It had 4 cases and one walkin chill box. But anyway. Do you have any videos on multi compressors systems or multi evp running off of one condenser. I couldnt find you email, the website wouldn't load
@antonalderliesten1421
7 ай бұрын
So there was potential floodback to the compressor but the TXV was only feeding vapor? Is there something i am missing cuz that seems wrong..
@overbuiltautomotive1299
4 жыл бұрын
hit it wuith uh hamnmer Z ole B.F.H that wull do it ;}......lol thank for upload sir A+..oh digital noo i hate digital but thats me i bought a 1953 Westinghouse i love it .the funny part its never been serviced that i know of looks stock lol..the big picture man i wish folks understood that stuff more instead of the deer in head lights look
@scmxrider613
5 жыл бұрын
add a ball valve in front of the drier.it`ll be your king valve
@Niveous23
5 жыл бұрын
ball valves are life.
@FireandFrostHVAC
5 жыл бұрын
What’s wrong with negative superheat??? 🤣🤣🤣 I prefer the Sporlan TX Valves too. And I agree with you about the wonky placement of the liquid service valve. I suppose that manufacturer installs filters that never need to be changed, so no need for a King valve then... good video, thanks Chris.
@44R0Ndin
4 жыл бұрын
"filters that never need to be changed" that's a good one! Just like you don't have to change the oil in your lawnmower anymore, just add more when it gets low. I still change the oil on my small engine equipment, and I bet I won't have to buy one for another 10 years (that's the secret, they can't sell more "durable goods" if they don't break, so they build them to break right after the warranty is finished!)
@kirkbethune682
Ай бұрын
Ac guys cause these issues gentleman always use the theory of keeping the integrity of the equipment for the next tech 😢😢😢😢
@lina98208
Ай бұрын
Digital thermostat breaks quit often compare to mechanical thermostat
@marriagepartnersministry5942
4 жыл бұрын
They get a second quote and that guy says the TXV is working fine, temp controller and solenoid are working fine, the contractor is dark but it working. So, the client doesn't want to spend a thousand bucks if he doesn't have to. If it keeps working what the client feels is fine then they assume you were wrong or trying to dip them off. A month to three later if it acts up again and the client uses garage logic and pegs you as an over do it sort of guy. How do you counteract client misjudgment like I just outlined above? My outline is a common occurrence in misjudgment around my part of the country.
@HVACRVIDEOS
4 жыл бұрын
I agree that they will often say but it's working......... all I can do is give them my honest opinion and let them make that decision.... luckily at this point and time i have a very good customer base that trusts me..... i say me because they often don't trust my employees and that is something i am working on....
@baladi921
5 жыл бұрын
I've been binging your videos. Thank you for keeping the beer cold and the food fresh, plus even though I don't understand a lot of this I do understand about the smaller stuff you talk about. Thanks man.
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@RobRocker09
8 ай бұрын
When you checked the copeland, did you check the resistance on the electrical terminals to determine it was good. .
@LC-qi5ff
10 ай бұрын
Do thermostats have a built-in differential, in this case 6F?
@coreybomhoff4784
8 ай бұрын
Sure would like an opportunity to work with you guys if I come to cali!
@OscarRodriguez-ik3vm
Жыл бұрын
Hello just a question, is there any reason you put the other pressure probe closer to the evaporator instead of putting in closer to the condenser? I see you had a T
@mainj54
5 жыл бұрын
I can never understand why someone would hang a coil and use nylon all thread , nuts and use plated washers. Whats the point if they are going to rust. Also having all that thread hanging down looks ugly.
@dirk_diggler320
5 жыл бұрын
Thanks for showing the flashing sight glass Chris. And I love the big picture diagnoses. I wish more techs used the same approach when diagnosing. My favorite is the guy who tells the customer it's going to be a quick fix cause its just a bad fuse. He acquires said fuse and to find a bad transformer or other component ..... Customer will never have confidence in that tech again ... Thanks for making your videos public and sharing your knowledge and approach.
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@dr650dualsport
5 жыл бұрын
Hey Chris! Love your videos and professionalism. Your customers could never question the approach you take. The videos prove it. Great tool for any tradesman to record his or hers service call. Cheers from Canada 🇨🇦
@hookedup9424
4 жыл бұрын
Have a 404a reach-in freezer the evaporator is icing up real bad I think it's the TXV
@hvacrnortheastern2110
5 жыл бұрын
No I am other tech that l don't like alco valve you can't take apart like a sporlan .Great video Chris.
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@andrewhicks6494
5 жыл бұрын
You could always use your pinch off tool on the liquid line after the receiver outlet if you needed to change the drier. I bought one after doing a pressure switch on a Mani and have used it at least 15 times that year, mostly to weld taps onto reach ins while they’re running because the saddle taps are worthless
@44R0Ndin
4 жыл бұрын
I've seen one of HVACR VIDEOS vids where he used a saddle tap on a piece of equipment that didn't have service ports. I'm not a HVACR technician, but I do auto repair so I do have the occasional contact with vehicle AC systems. IMO, saddle taps should only ever be used to remove the charge from equipment that doesn't have service ports, and never left in place. That rubber you wrap around the pipe will degrade, and those screws are all that's compressing the rubber to seal it against the pipe, and a dirty pipe won't seal as well, and... well a leak is basically inevitable, and likely created when you install it. So it's best to use it as little as possible, and never left in the system as a permanent fitting. If I was working on something that didn't have service ports, and I needed access, I'd use a saddle tap. Once I was done, I'd recover the charge, then sweat in a pair of service ports. I don't like the idea of a pinch off tool on copper lines as it puts the copper thru so much stress that I'd never trust that section of pipe again (work hardening and micro cracking are likely at the corners of the pinched-off pipe). As far as I've seen from watching many videos, when I see a pinched off copper line it's also sweated shut. That's acceptable for long term use, but I only trust it because I've seen them that way from the factory. Even in plumbing saddle taps are a common source of water leaks, usually behind the fridge as some DIY'er decided that was the quick and cheap way to get a water line connected to the fridge's ice maker. The leak can happen any time from under a month to a couple years after installation, but it WILL eventually happen.
@ljmanz55
3 ай бұрын
Please don't use UEI products they are trash
@julianfigueroa9525
4 жыл бұрын
Why does the ceiling of a walk in freezer box is always frosted? Is it bad door gaskets? If not what other things you look for to cause frost in the ceiling of freezer hope it’s not a dumb question?
@flyinbrianvids
5 жыл бұрын
Hey, I just heard that the SMAN380/480 will link up to measurequick now.
@HVACRVIDEOS
5 жыл бұрын
yep that is confirmed! I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@didijiji918
5 жыл бұрын
I agree with you, there is some moisture in the refrigeration line and ice clog at the metering device, the line should be vacuumed and refilled by the fresh refrigerant. I like your video, you did a great job.
@BYENZER
3 жыл бұрын
YOU CRUSHED/BROKE UP AN ICE PLUG IN THE TXV. DONE.
@chriszachem2012
3 жыл бұрын
thanks straight forward, good learning exp.
@HVACChillin
5 жыл бұрын
Why would you go back with a flare style drier? Just preference?
@HVACRVIDEOS
5 жыл бұрын
Yeah preference, I'm lazy and dont want to have to bring my torches up on the roof next time to change the drier......
@syafiisiregar3391
5 жыл бұрын
Teks Indonesia please
@texastyrannyresponseteam794
Жыл бұрын
We all find the brands/models that we have good experiences with.. Thats what we stick with because we can say with no reserve that they will do the job and serve the client well... Thats true of whatever business you are in... And the way it should be.... If you only sell what's cheap or what makes the most profit right now... That a recipe for disaster... Typically a client will trust you and when your recommendation proves true... You keep that client for life.. and equally important... they send referrals... There no better business than repeat and referrals... The cost of client acquisition is free (or cheap) and they are usually the best clients.... Once again... This is true whatever line of work you are in... Thanks for the content..
@albertoldschool6950
5 жыл бұрын
How many ways can you say you don't like Emerson valves, Let us count.
@HVACRVIDEOS
5 жыл бұрын
You can add emerson driers and sight glasses and danfoss txv's to that list too.
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@sterlingarcher46
5 жыл бұрын
@@HVACRVIDEOS Duuuude , Danfoss is all we have around here ! Well , not really, but it's the number 1 brand , most Txvs I see are Danfoss.
@James_Bowie
5 жыл бұрын
Why suggest changing all of those other parts when it seems that a TXV and contactor change out will do the job?
@HVACRVIDEOS
5 жыл бұрын
I will answer your question on my stream tonight, I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@victorleon1563
3 жыл бұрын
Why would you think its under charged when it's freezing back to the compressor. I would have gone straight to the tev ❓
@jonjordan6606
3 жыл бұрын
I’m a newbie, and I have a walk-in cooler that is running off a halfhorsepower Compressor and it does not seem to get below 50° the charge seems fine, should I adjust the TXV before trying something else or should I get a bigger condensing unit
@MAKCOH818
4 жыл бұрын
My compressor overheats in about 20min
@ovidiocabrera1979
3 жыл бұрын
High superheat!!!
@ΗλιαςΜπελος-σ1ψ
5 жыл бұрын
Good morning from Greece Chris.I have some castomers here that they have some junk equipment like this and it's a pain in the ass, but we're technicians and we have to fix them to,with the lowest price always! Keep on the good work my friend.
@HVACRVIDEOS
5 жыл бұрын
Thanks for watching! I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@cshin58
Жыл бұрын
Hi, Chris, just watching your video and I think I’m having similar issues wit subway sandwich maker , R404 and pressure looks good, but temperature is staying at 47 , 35 low 225 high condenser coil is clean , made turn few to the left and more to the right , but no changes on pressure at all, took out all refrigerant and weigh charged of 25 oz. But temperature maintains 48 degrees, would it be the TXV ? Thank you in advance!
@tytig94
5 жыл бұрын
Your channel makes me want to go look for another company to work for. The company I work for only does residential. I want more variety!!!
@thefambam9305
5 жыл бұрын
I know right! My last day at my residential company is this Thursday, will be starting at a commercial, refrigeration company friday.got 5 years in residential
@noticiasdigitalhilder1226
2 жыл бұрын
Hi Mister I have wall in freezer is working + 10 F have to work -05 I have manifold regular yellow jaket hi presusure 325 psi on low 20 psi. What presure is normal on Hi? What presusure in low? Thanks for help me
@kingsolo6241
4 жыл бұрын
Emerson owns almost everything HVAC. That’s the sad reality.
@MARLON4701
3 жыл бұрын
American market maybe.. Here in europe its mostly danfoss
@kingsolo6241
3 жыл бұрын
@@MARLON4701 Emerson owns Danfoss as well. Just pull up Emerson ownership of Danfoss.
@bcbottoms
2 ай бұрын
What mfg and model digital thermostat do you recommend for medium temp systems (+35° holding temp).
@johntaylor4854
11 ай бұрын
I’m not sure if it’s been mentioned in the above comments so i apologise if I’m repeating anyone else. The equaliser line is positioned incorrectly, when the valve & orifice are sized correctly (hopefully always) that will cause you problems every time. Obviously there is some liquid Cary over through the equalising line and when your bulb is positioned down circuit from that your creating a false superheat causing the valve to shat down equivalent initially then behave IRAtic with the fluxeration and what not.
@terryj.macmullen9968
3 жыл бұрын
sometimes i ve seen low superheat at compressor caused by coax heat exchangers leaking internally. liquid dumping directly into suction line.
@yoyofd
5 жыл бұрын
Do you do the same calc from ac to get that target sh ? Thanks
@yoyofd
5 жыл бұрын
Can you ad it to your next video?
@suezq74
5 ай бұрын
Riley: From my HVAC knowledge as an autistic 13yr old, Superheat is very important. Dangerously low superheat can make liquid reach the compressor and potentially kill it. Dangerously high superheat signals that the system is low on refrigerant. - Riley
@suezq74
5 ай бұрын
1:02 That’s why my fictional HVACR company, Losense strives to fix those wrongs. We manufacturers at Losense work for a long time to make it a polished product. FYI, Losense is my fictional HVACR, appliance and technology company. The name “Losense” came from hisense so credits to Hisense for the trademark. - Riley
@Eddy63
5 жыл бұрын
Your voice sounds like the lead singer in the band Sister Hazel ... Just an observation ... The song is All for you ... Good vid also ...
@HVACRVIDEOS
5 жыл бұрын
Ha Ha I loved that band and song, too bad I cant sing to save my life......... I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@Fishing570
Жыл бұрын
i have a question. We have a quadruple-door Supera freezer that has been running a lot colder than it is currently set to run. What would be the main cause of this?
@ovidiocabrera1979
3 жыл бұрын
Congratulations you are a very knowledgeable technician, and well explained. I hope you are been taking care $.
@robbygraves739
5 жыл бұрын
Nice work brother. Ive never thought about running the adjuster in and out to free up a valve in a pinch. Awesome video.
@robanderson84
5 жыл бұрын
really similar to valves i deal with in plumbing/water lines at work, it is called "exercising the valve", which oddly enough an electrician contractor taught me for breakers, but he said plumbing is same, they all like to be turned on all the way and turned off all the way- back and forth a few times- at least once a year, or they get gummed up or rust or whatever, so at least once a year turn whatever valves you have folks.... it has worked wonders for the old building i take care of, saves lots of replacement work and when a pipe breaks, the valve actually shuts off the water
@johng5295
3 жыл бұрын
Thanks in a million. Great content.
@ninamcclure2193
3 жыл бұрын
Great video guy, I know you put in a lot of time and effort into making these and it is appreciated. I wonder if you have ever set up a white board and explained how the refrigerant flows through the system. This may not be your thing but you do have a good teaching skill. Working with auto a/c is so much easier as in less parts and it's just basic. When I'm watching you work with these systems I'm like damn I cant keed up with all the stuff that's added. Defrosting and a/c power and all these switches everywhere. Lol. I'm starting to pick it up though thanks to you.
@DWAYNE2ism
4 жыл бұрын
Great video The oil concern youu had. About compressor did you charge with oil?
@JohnnyFlips
5 жыл бұрын
i need to figure out a career
@tyhuffman5447
5 жыл бұрын
I go back to the old saying that the machine always tries to tell us what is wrong, the hard part is we don't speak Machine very well. In this case the valve that sounded odd was the problem area. My guess is this is more normal than abnormal. Good job troubleshooting. Maybe it was just my ears playing tricks but those fan bearings on the roof didn't sound great. Probably just my ears.
@coolezum
5 жыл бұрын
Another top notch diagnosis and procedure, brother.👍
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@lerch400block
3 жыл бұрын
You should never have to adjust the valve, unless it's a new install or hasn't worked right from the get go.
@CoffeeQuilava
5 жыл бұрын
@HVACR VIDEOS I have a question, I have a heat pump that is not keeping my house cool. I hade someone come out and I have a low super heat, and flooding the A coil, I have the correct charge, clear site glass, and clean coils. the condenser is discharging warm air, the tech could not figure it out, any recommendations. ps love the vids
@whitesheatingairappliancer7101
5 жыл бұрын
Dave your residential heat pump has a sight glass? I did not know that would benefit the equipment.
@Josh-px6xb
5 жыл бұрын
Could it be the txv?
@CoffeeQuilava
5 жыл бұрын
@@whitesheatingairappliancer7101 installer added it wean he installed the system, he said it helps diagnosing future problems. I thought the same thing, but It didn't cost me anything for him to add it that I know of
@CoffeeQuilava
5 жыл бұрын
@@Josh-px6xb I don't think I have one. I think its a orface tube.
@HVACRVIDEOS
5 жыл бұрын
I will answer your question on my stream tonight, I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@chriscooley906
5 жыл бұрын
Great instructional video Chris, Great diagnosing, keep up the stellar work bud!
@HVACRVIDEOS
5 жыл бұрын
Thanks bud, I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@slamdvw
5 жыл бұрын
you can tell it's happier... it's building frost after the expansion valve, and not up at the compressor. thanks for sharing!
@workinprogress008
4 жыл бұрын
1.9° subcooling you mean? In the suction line
@shanebehm8251
4 жыл бұрын
Sooo many guys think that ice on the compressor head means that it's flooding back. Thanks for clearing this up!!👏
@HVACRNorth
5 жыл бұрын
i love going in walk ins with you. good job bud
@tolsonsmith9121
3 жыл бұрын
Since your recovering the charge, do you plan on installing a king valve at the accumulator so you can change the drier in the future?
@eclipse369.
3 жыл бұрын
digital temp control? BLEH im a fan of mechanical over digital
@larrykuzniar6204
3 жыл бұрын
excellent videos , you are teaching me so much. thank you
@rolandgirouard5914
4 жыл бұрын
Good boy I like techs that know how to make a bill.
@HVACRVIDEOS
4 жыл бұрын
I will be going live on KZitem this evening 11/25/19 @ 5:PM (pacific time) to discuss my most recent uploads, and answer questions from email’s , KZitem comments, and the Live chat come on over and check it out if you can. kzitem.infolive
@craigspicer4296
3 жыл бұрын
It was great to watch this and i pick something up i never would have thought to do. Thank you for your time and experience
@victorleon1563
3 жыл бұрын
The worsted place to mount a thermostat is in the actual freezer room.
@roberthvacpro
5 жыл бұрын
You’re working under the assumption the TEV was ever properly calibrated
@HVACRVIDEOS
5 жыл бұрын
True
@jacquesdaoud4263
3 жыл бұрын
Thank you .you just answered my question
@wonderhomie2011
5 жыл бұрын
Contaminated refrigerant. Lucky the customer didn’t loose the compressor.
@primetime758
5 жыл бұрын
r u new?
@ferozkhan9735
4 жыл бұрын
Sir I requested you to make a video on plate freezer
@zekenzy6486
5 жыл бұрын
I love to watch your video. I'm learning HVACR now. I wish you can post shared 2 video everyday . so I can watch and learn more HVACR . Thanks you for shared
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@nathanbelden8269
5 жыл бұрын
Pretty sure I sent email about shirt did u already start replying to those? Love your videos !!
@HVACRVIDEOS
5 жыл бұрын
I'm out of shirts but I am working on placing another order and figuring out a better way to distribute them so stay tuned.....
@nathanbelden8269
5 жыл бұрын
Dang I email during that stream when u mentioned it. Ok I keep a look and eat out.
@bq2appliances15
3 жыл бұрын
man your videos are so helpful thanks all the time
@emptech
5 жыл бұрын
I understand the industry likes to see a compressor superheat of 10 plus or minus a couple (F). The system SH is measured from the suction line 8 inches or so before the suction input of the compressor. What system superheat would you like to see as a minim?
@HVACRVIDEOS
5 жыл бұрын
I will answer your question on my stream tonight, I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@FamilyChannelfun32
3 жыл бұрын
Any ideas on what unit I can use for a food cart. I want to build a walk in freezer inside of it. I am a plumber and have done some hvac. By no means am I a pro!
@FamilyChannelfun32
3 жыл бұрын
?
@sterlingarcher46
5 жыл бұрын
There's one thing I can't wrap my head around : if the txv is acting up , why would it cause a low subcool and a flashing sight glass ? I tried but I just don't get it , can you put me out of my misery , Chris ? Thanks again.👍
@Niveous23
5 жыл бұрын
I'd like to know as well. I'm still new to everything. Is it maybe that w/e caused the txv to be sticky also caused a partial restriction beforehand?
@myoung99wood
5 жыл бұрын
If the coil was flooded and as a result more of the refrigerant was in the evaporator then can that may have caused a slight deficiency upstream in the system ??
@myoung99wood
5 жыл бұрын
Oops...delete the word "may" from my previous comment
@didijiji918
5 жыл бұрын
The TXV acts as an adjusted gate and makes the refrigeration flow slow down, but the over-opened TXV causes too much flow into the evaporator coil, and the less liquid stores in the condenser coil, and thus, the over-speed liquid flow passing throw the evaporator coil ( the pressure can't drop to the ideal point), so it brings very low superheat, the saturated gas and liquid absorb the heat in the suction line, so you can see ice covering the line, and it could hurt the compressor very much.
@sterlingarcher46
5 жыл бұрын
@@didijiji918 yeah , mate , I understand that, that's not my issue here . My issue is with the low subcool . Thanks anyway , mate , cheers .
@jamesmclaughlinprimitivele4587
4 жыл бұрын
Looked like valve was all the way open
@harrydickson4575
5 жыл бұрын
Excellent video and job 👍👍👍👍
@brandonunderwood4224
3 жыл бұрын
Have a new WI Frz installed in NOV 2020. 2 weeks ago I got my first call saying box temp 20°. Bubbles in sight glass so I cleared it with 1lb 404. My diagnosis was that whoever installed it did not properly charge it and are just now seeing a problem due to higher ambient temps. I've done a leak check as well. Am I on the right track?
@stephenramsey9304
5 жыл бұрын
Why didn’t you check the sub cooling ?
@jjjames5089
Ай бұрын
I enjoy your content just don't stop being detailed while you work explaining your thoughts process. Thanks
@phareztrinimand
2 жыл бұрын
Hello question, my country is mostly summer, I have two choices of TXV, one with 4 superheat and the next with 8, would the 4 produce cooler air at the evaporator than the 8?, It`s r134a
@mcvaylitt
5 жыл бұрын
Should check compressor return temp is above 30.
@HVACRVIDEOS
5 жыл бұрын
I will be going live on KZitem this evening 8/19/19 @5:pm (pacific time) to discuss my most recent uploads and answer questions from KZitem comments, the chat, and emails. Come check it out if you can kzitem.info/news/bejne/xHyMsHuiZn2HeJg
@steevydance
Жыл бұрын
You are the best ❤🙏🏿
@sampathravindra8676
4 жыл бұрын
Hi Good day sir..i Have learned liquid is worst enemy for compresure..but i can see u adding liquid to the suction line..may i know is it correct...Thanks for video..
@alicepet1994
5 жыл бұрын
Can you use Pinch off tool to change the filter drier without have to recovery?
@HVACRVIDEOS
5 жыл бұрын
yeah you could but it will look like crap
@sterlingc107
2 жыл бұрын
What size reefer wrench do you need for the TXV adjustment screw? Is it 3/16ths? Thanks for the videos.
@serengetimanstnik6369
2 жыл бұрын
That defrost looks like it got a little sparky
@Karnol428
Жыл бұрын
How do you know what target superheat to go for?
@levy5867
5 жыл бұрын
What else to say than excellent video!
@derrickgarcia303
4 жыл бұрын
What would you recommend on compressor superheat for -10 walk in freezer? Thanks!
@HVACRVIDEOS
4 жыл бұрын
About 6 degrees evap superheat