FMS Integration shows you how to update the Eaton PDI Wavestar BCMS current rating. The PDI Wavestar BCMS or branch circuit monitoring system does not allow you to edit the CT rating from the local display.
There are three options when updating the current rating on a PDI BCMS.
1. Write or set from your Remote Monitoring System
2. Using the PDI branded software, connect to the BCMS board.
3. Using third-party software, write the correct value via Modbus.
We show using Modbus Poll from Modbus Tools in this example. This does not require removing any panels from the unit. You can update this via the ethernet port using Modbus TCP or the serial port using Modbus RTU.
The BCMS monitor is used on the PDI RPP and PDI PDU.
So if you have been struggling with clearing alarms from the local display because of the default 20 amp current rating. This is a non-invasive way to update the breaker amperage setting.
We understand not all applications are the same. If you have any questions, please feel free to contact us.