Setup if using output 2 as a switched DC to drive SSR to drive heater.
For temperature controller 1ET05225 (PM6C1EC-AAAAABA)
Step 1:
To enter set up menu push and hold the up and down arrow keys for approximately 3 seconds, LoC is displayed on the lower display.
Step 2:
Once there, push the green advance key a number of times until Fn1 displayed on the lower display, then use the down key to select the function of output 1 which is on the upper display, select Off as this output is not been used.
Step 3:
Push the green advance key once until Fn2 is displayed on the lower display, then use the down key to select the function of output 2 which is on the upper display to to hEAt -- Heating.
Step 4:
Push the green advance key once until h.A9 is displayed on the lower display, then use the down key to select the control method which is on the upper display to select Pid , PID control.
Step 5:
You can return to the default display by pushing the infinity key.
Step 6:
To do a Autotune, push the advance key once and AUt is displayed on the lower display, then use the down key to start the autotune which is yES on the upper display. Autotune process may take up to 1 hour depending on
Step 7:
To prevent anyone from changing settings, enter set up menu push and hold the up and down arrow keys for approximately 3 seconds, LoC is displayed on the lower display. Then use the down key to select the lockout menu level to prevent anyone from changing settings on the upper display to 2. This can be reset to 5 if you want to change settings at a later stage.
Step 8:
You can return to the default display by pushing the infinity key.
For more Information Visit: www.cynebar.com.au/