Cynebar Temperature Controller 1ET05225 (PM6C1EC-AAAAABA) Setup for an RTD/PT100 Input.
ALL WIRING SHOULD BE DONE BY A LICENSED ELECTRICIAN!
Step 1:
To enter set up menu push and hold the up and down arrow keys for approximately 3 seconds, LoC is displayed on the lower display.
Step 2:
Once there, push the green advance key once to SEn displayed on the lower display, then use the down key to select the sensor type which is on the upper display.
Set to rO.1H -- RTD / PT100.
Step 3:
Push the green advance key twice until C_F is displayed on the lower display, then use the down key to select the display units which is on the upper display to select C which is °C.
Step 4:
Push the green advance key once, r.Lo is displayed on the lower display, then use the down key to select the low range of the set point which is on the upper display.
Usually this is 0 °C
Step 5:
Push the green advance key once, r.hi is displayed on the lower display, then use the down key to select the high range of the set point which is on the upper display.
Usually this is a extra safety measure for you to set the highest temperature you would want the operator's to use in °C. You may however prefer to set this higher so as not to limit use of temperature controller for higher temperatures later on.
Step 6:
You can return to the default display by pushing the infinity key.
For more information visit: www.cynebar.com.au/